Power Factor Correction Calculator (UK, 400 V 50 Hz)

Size a capacitor bank in kVAr for a 400 V, 50 Hz supply, see the µF per capacitor and where excess reactive power charges on business DUoS bills come from.

The interactive tool loads here when JavaScript runs.

About this tool

What is the Power Factor Correction Calculator?

On a half-hourly metered business supply in Great Britain, poor power factor can show up on the distribution use-of-system part of the bill as an excess reactive power charge. Charging statements have historically set the trigger at an average power factor of about 0.95 (Western Power Distribution's 2012 East Midlands statement is one example), but the threshold, rate and assessment period are set in your DNO's current charging statement, so check its reactive power clause. This version opens on a 400 V, 50 Hz delta bank aimed at 0.95.

Enter the site's average kW and the power factor from the bill or a logger, and the calculator returns the kVAr of correction, the capacitance of each capacitor at 50 Hz and the drop in current and kVA. A 200 kW load at 0.82 needs 73.9 kVAr to reach 0.95, and the current falls from 352 A to 304 A.

That freed capacity often matters as much as the reactive charge. If the site is close to its agreed maximum import capacity in kVA, correction can buy headroom without a new connection offer from the DNO.

  • kVAR from kW and two power factors, with the catalogue multiplier
  • Capacitance per capacitor for single-phase, delta and star at 50 or 60 Hz
  • Current, kVA and cable loss before and after
  • Scaled power triangle
  • Warnings for over-correction targets
Read the guide: Power Factor Correction: Sizing Capacitors in kVAR and µF

Updated

How to use the Power Factor Correction Calculator

  1. Enter the real power in kW. Use average demand from a bill or logger rather than a nameplate total.
  2. Enter the existing power factor and the target. 0.95 is a common target; going past 0.98 rarely pays and risks over-correction at light load.
  3. Enter the voltage (line to line for three-phase) and frequency.
  4. Choose single-phase, three-phase delta or three-phase star for the capacitor connection.
  5. Read the kVAR, the capacitance per capacitor, the current before and after, and the released kVA.

Worked examples

Factory unit at 0.82, target 0.95

Input

200 kW, PF 0.82 to 0.95, 400 V, 50 Hz, delta

Output

73.86 kVAr; 489.8 µF per capacitor; 352.0 A to 303.9 A; 243.9 kVA to 210.5 kVA

About 33 kVA of capacity is released. A bank of 75 kVAr in automatic steps would be the usual choice, so that correction follows the load through the day.

Going further, to 0.97

Input

200 kW, PF 0.82 to 0.97, 400 V, 50 Hz, delta

Output

89.48 kVAr; 297.6 A

The extra 15.6 kVAr saves only 6 A more. Unless your DNO's charging statement sets its reactive threshold above 0.95, the extra steps pay back only through capacity and a small cut in cable losses.

Single 2.2 kW motor at 230 V

Input

2.2 kW, PF 0.75 to 0.95, 230 V, 50 Hz, single-phase

Output

1.22 kVAr; 73.2 µF; 12.75 A to 10.07 A

Capacitors fitted at a motor must stay below its no-load magnetising kVAr, or the motor can self-excite when it is switched off. Many sites correct at the main board instead.

Background and insight

Induction motors, transformers and fluorescent ballasts draw magnetising current that lags the voltage. That reactive current does no work, but it flows through every cable and transformer between the source and the load. Power factor, PF = kW ÷ kVA = cos φ, measures how much of the current is useful. Many utilities add a charge when the monthly PF falls below a threshold, commonly 0.9 or 0.95, or bill on kVA demand.

A capacitor draws leading reactive current that cancels part of the lagging current. With real power P unchanged, the reactive power before correction is P × tan φ1 and after is P × tan φ2, so the capacitor must supply Qc = P × (tan φ1 − tan φ2). Raising 100 kW from PF 0.70 to 0.95 needs 100 × (1.0202 − 0.3287) = 69.15 kVAR. Current falls in proportion to PF1 ÷ PF2, here by 26%, and cable losses (proportional to current squared) fall by about 46%.

Capacitance follows from Q = V² × 2πf × C for each capacitor. A single-phase capacitor across V needs C = Q ÷ (2πfV²). In a three-phase delta bank each of three capacitors sees the full line voltage and supplies Q ÷ 3, so C = Q ÷ (3 × 2πf × V²). In a star bank each sees V ÷ √3, which makes each capacitor three times larger: C = Q ÷ (2πf × V²). Delta banks are therefore usual at low voltage. Standard references include IEEE Std 18 for shunt power capacitors and IEC 60831 for low-voltage self-healing units.

Common use cases

  • Avoiding utility PF penalties

    Size a capacitor bank to keep the monthly power factor above the tariff threshold.

  • Freeing transformer capacity

    See how many kVA correction releases before buying a larger transformer.

  • Motor capacitor selection

    Find the µF for an individual motor capacitor at 50 or 60 Hz.

  • Teaching the power triangle

    Show how kW, kVA and kVAR relate before and after correction.

Tips and limitations

  • Look at the reactive units (kVArh) and active units (kWh) on the half-hourly data, and compare them with the excess reactive power clause in your DNO's current charging statement.
  • Variable speed drives, LED drivers and UPS units add harmonics. Where they are a large part of the load, specify a detuned bank with reactors; a plain bank can resonate with the supply transformer.
  • Check which period the reactive charge is assessed over in the charging statement. A good monthly average can still hide poor half-hours.
  • Low-voltage capacitor units are made to IEC 60831-1; check that their rated voltage covers the top of the 230 V +10% supply tolerance, plus any harmonic voltage.

Sources and further reading

  1. Use of System Charging Statement, WPD East Midlands, effective 1 April 2012 (historical example), National Grid Electricity Distribution (formerly WPD). Section 2.37 shows how an excess reactive power charge was set in 2012. It is not current; use your DNO's current statement, published each April.
  2. DCUSA DCP222: non-billing of excess reactive power charges, Ofgem. Removes the charge for CDCM generators asked by their DNO to run below PF 0.95.
  3. The Electricity Safety, Quality and Continuity Regulations 2002, regulation 27, legislation.gov.uk. 230 V and 50 Hz declared supply and its tolerances.

Frequently asked questions

What power factor triggers a reactive power charge in the UK?

Distribution use-of-system charging statements include a charge in pence per kVArh for excess reactive units, and statements have historically set the trigger at an average power factor of about 0.95. Check the reactive power clause in your DNO's current charging statement, published each April, for the threshold, the rate and the period it is assessed over.

Do domestic customers pay for poor power factor?

No. Domestic bills are in kWh with no reactive power charge, so a household gains nothing from correction. The excess reactive power charge is for business supplies; your DNO's charging statement lists the tariffs it applies to.

Is it worth correcting to unity?

Rarely. Once the site is above the threshold in your DNO's charging statement, the reactive charge is gone and more capacitance mostly risks a leading power factor at night or at weekends, when the motors stop but the bank stays on. Automatic banks switch steps out as the load falls.

Can power factor correction lower my capacity charge?

It lowers the kVA the site draws for the same kW, which can let you agree a lower maximum import capacity at your next review, or avoid exceeding it. Whether that saves money depends on your DNO's capacity charges and on how close you are to the limit.

Should I use 50 Hz or 60 Hz?

Always 50 Hz in Great Britain. Using 60 Hz would underestimate the capacitance needed by a sixth.