Water Pipe Size Calculator for CPVC and GI Pipes (India)

Choose ½", ¾" or 1" CPVC (IS 15778 SDR 11) or GI medium (IS 1239) pipe for a flow in litres per second, and see how much overhead tank head the run uses up.

The interactive tool loads here when JavaScript runs.

About this tool

What is the Water Pipe Size Calculator?

Most Indian homes draw water from an overhead or terrace tank, not straight from a pressurised main. The only pressure at a tap or shower is the height of the water in the tank above it, often 2 to 4 m on the top floor of a building. Pipe size therefore decides whether the top-floor shower trickles, and the useful answer is the friction loss in metres of head, which this version shows next to the bore.

It picks from the pipes Indian plumbers buy. CPVC hot and cold water pipe to IS 15778 is sold by nominal size (15 mm or ½", 20 mm or ¾", 25 mm or 1"), but its SDR 11 walls are thick: a ½" pipe is 15.9 mm outside with only about 12.5 mm of bore at the minimum wall. Makers list walls above the minimum, so real pipes may be up to 1 mm smaller in bore (11.5 mm for ½") and lose up to about half as much again as shown here. Older buildings and risers use GI tube to IS 1239 (Part 1), medium grade, where 15 NB has a bore of about 16.2 mm.

  • Minimum inside diameter from flow and maximum velocity
  • Published inside diameters for copper L and M, PEX SDR 9, PVC and steel Schedule 40
  • Actual velocity and Hazen-Williams friction loss with editable C
  • Total loss over a length in psi, kPa and head
  • Side-by-side comparison of every material for the same flow
Read the guide: Water Pipe Sizing by Velocity and Hazen-Williams Friction Loss

Updated

How to use the Water Pipe Size Calculator

  1. Keep SI units and the India tube standard, then pick CPVC or GI.
  2. Enter the flow in litres per second. The examples assume about 0.1 L/s for a basin tap and 0.2 L/s for a shower; use the outlet maker's rated flow if you have it, and more for a line serving a whole bathroom.
  3. Set a modest maximum velocity, such as 1.5 m/s, for quiet pipes.
  4. Enter the run length from the tank, read the loss in metres of head, and compare it with the height of the tank's lowest water level above the outlet.

Worked examples

Top-floor shower from a terrace tank

Input

0.2 L/s (assumed shower flow), 12 m of CPVC from the tank, 1.5 m/s limit

Output

¾" CPVC (18.2 mm bore): 0.77 m/s, 0.50 m of head lost; ½" CPVC would lose 3.13 m

A ½" line would run at 1.63 m/s, just over the limit, and its friction exceeds the 2 to 3 m of head a terrace tank gives the floor below, so the shower would barely run. The ¾" line leaves most of the head for the shower.

Old GI line to the same shower

Input

0.2 L/s, 12 m of GI medium, C 120

Output

15 NB (16.2 mm bore): 0.97 m/s, 1.34 m of head lost

New GI loses more than CPVC of a similar bore because it is rougher, and old GI that has scaled up inside loses more still. When replacing GI with CPVC, going up one size is common.

Bathroom down-take for a flat

Input

0.5 L/s, 15 m, 1.5 m/s limit

Output

CPVC 1" (23.4 mm bore): 1.16 m/s, 1.01 m lost. GI 20 NB: 1.35 m/s, 2.20 m lost

With ¾" CPVC the velocity would be 1.92 m/s and the loss 3.43 m, more than many overhead tanks can spare.

Background and insight

Nominal sizes are not inside diameters. Copper tube to ASTM B88 has an outside diameter 1/8 in larger than its nominal size, and type K, L and M differ only in wall thickness, so type M has the largest bore. PEX to ASTM F876 uses the same copper tube sizes (CTS) outside but a much thicker SDR 9 wall, so 3/4 in PEX has an inside diameter of only about 0.68 in. Schedule 40 PVC and steel pipe follow the iron pipe size system, where 3/4 in nominal has a 1.050 in OD and a 0.824 in ID.

Velocity limits protect against noise, water hammer and erosion of the pipe wall. The Copper Development Association and the Uniform Plumbing Code limit copper systems to 8 ft/s (2.4 m/s) for cold water and 5 ft/s (1.5 m/s) for hot water, and the CDA recommends 2 to 3 ft/s above 140 °F, where erosion corrosion is faster. Many designers keep residential branches nearer 4 ft/s for quiet.

Friction loss here uses the Hazen-Williams formula, an empirical fit for water at ordinary temperatures in turbulent flow. Its roughness constant C is about 150 for new plastic pipe, 140 for copper, 120 for new steel and 100 or less for old corroded steel. In US units, head loss per 100 ft = 0.2083 (100/C)^1.852 x gpm^1.852 / d^4.8655. Because loss scales with almost the fifth power of diameter, going up one pipe size typically cuts friction by more than half.

Common use cases

  • Residential water service and mains

    Check that a service line or main carries the peak demand without exceeding the velocity limit or losing too much pressure.

  • Copper to PEX substitutions

    See which PEX size matches the bore of an existing copper line before a repipe.

  • Hydronic and process loops

    Pick a pipe size for a circulator flow at a target velocity, then read the head loss for pump selection.

  • Irrigation and outbuildings

    Size a PVC run to a garden, barn or workshop and estimate the pressure left at the far end.

Tips and limitations

  • Measure head from the lowest working water level in the tank, not the top, because pressure falls as the tank empties.
  • Pressure pumps on the outlet or a booster change the sums; enter the pump's pressure as the head available.
  • SDR 13.5 CPVC has thinner walls and a slightly larger bore than SDR 11; this table uses SDR 11, the common choice for hot water.
  • Insert fittings and elbows add loss. Add about a quarter to a half of the straight length as an allowance for a typical bathroom.

Sources and further reading

  1. Galvanized Iron Pipes (GI): dimensions of medium steel tubes as per IS 1239, Public Health Engineering Department, Government of Meghalaya. Dimensions per IS 1239 (Part 1): outside diameter range, thickness and mass for 15 to 150 NB medium tubes.
  2. CPVC pipes: dimensions to IS 15778 (SDR 11 and SDR 13.5), Finolex Industries. Dimensions per IS 15778, as published by the maker: mean outside diameter and wall thickness by nominal size. The calculator uses the minimum wall.

Frequently asked questions

Which is better for a shower line, ½ inch or ¾ inch CPVC?

From an overhead tank, ¾ inch for anything but a very short run. At 0.2 L/s a 12 m run of ½ inch CPVC loses about 3.1 m of head against 0.5 m for ¾ inch.

What is the inside diameter of ½ inch CPVC pipe?

IS 15778 SDR 11 pipe of ½ inch (15 mm) nominal size has a mean outside diameter of about 15.9 mm and a minimum wall of 1.7 mm, so the bore is about 12.5 mm at the minimum wall. Makers list walls of 1.7 to 2.2 mm, so a real pipe may be as small as 11.5 mm inside and lose up to about half as much again (4.70 m instead of 3.13 m at 0.2 L/s over 12 m).

What are the dimensions of 15 NB medium GI pipe?

IS 1239 (Part 1) medium tube of 15 mm nominal bore has an outside diameter between 21.0 and 21.8 mm and a 2.6 mm wall, so about 16.2 mm inside. The grade is marked with a blue band.

How much pressure does an overhead tank give?

About 9.8 kPa, or 0.1 kg/cm², for every metre of height between the water level and the outlet. A tank 3 m above a shower gives about 0.3 kg/cm² before any pipe friction.

Why is GI being replaced by CPVC in homes?

GI corrodes and scales inside over time, which narrows the bore and raises friction, while CPVC stays smooth. For the same nominal size, though, SDR 11 CPVC has a smaller bore than GI, so check the size rather than swapping like for like.

Is there an in-depth guide to the Water Pipe Size Calculator?

Yes. “Water Pipe Sizing by Velocity and Hazen-Williams Friction Loss” covers the background, how it works, common pitfalls and worked examples. Read the full guide.