Australia version. Rooms in metres and fans in L/s and m³/h, with the NCC Housing Provisions 10.8.2 exhaust minimums for bathrooms, laundries and kitchens. US version
Air Changes per Hour and Exhaust Fan Calculator (Australia)
Turn a bathroom, laundry or kitchen exhaust fan rating in L/s into air changes per hour, and check it against the NCC 25 L/s and 40 L/s minimums.
The interactive tool loads here when JavaScript runs.
About this toolWhat is the Air Changes per Hour Calculator?
Since NCC 2022, exhaust fans in Australian homes have minimum flow rates. Housing Provisions 10.8.2 asks for 25 L/s in a bathroom or sanitary compartment and 40 L/s in a kitchen or laundry, and the air must go straight to outdoor air through a duct or shaft, not into the roof space.
Fan boxes in Australia usually quote m³/h, so a fan sold as 250 m³/h moves about 69 L/s, while a cheap 90 m³/h ceiling fan sits right at the 25 L/s bathroom minimum. This calculator converts between the two and shows what the flow means as air changes per hour for your room, which is a better guide to how fast steam clears than the litres per second on their own.
The rate is the floor, not the target. A small ensuite at 25 L/s turns its air over almost 14 times an hour, while the same fan in a 2.4 by 2.0 m bathroom manages less than eight.
- ACH from airflow or airflow from a target ACH
- Room volume from dimensions or entered directly, in feet or metres
- Airflow in cfm, m³/h and L/s together
- ASHRAE 62.2 whole-house ventilation rate from floor area and bedrooms
- Guidance table from CDC, ASHRAE 62.2, ASHRAE 170 and IECC with sources
Updated
How to use the Air Changes per Hour Calculator
- Keep the units on metric and enter the room length, width and ceiling height in metres.
- Choose "ACH from airflow" and enter the fan's rated flow in m³/h (L/s times 3.6).
- Compare the L/s result with 25 L/s for a bathroom or toilet and 40 L/s for a kitchen or laundry.
- To size a fan for a target, switch to "Airflow for target ACH" and read the L/s it needs.
Worked examples
Bathroom fan at the NCC minimum
Input
Bathroom 2.4 x 2.0 x 2.4 m, fan 25 L/s (90 m³/h)
Output
11.5 m³; 7.81 ACH, one air change every 7.7 minutes
The fan meets 10.8.2. If the bathroom has no openable window, the fan must also be wired to the light with a 10 minute run-on timer and have make-up air, for example a door undercut.
Range hood in an open-plan kitchen and living area
Input
Kitchen and living 7.0 x 5.0 x 2.7 m, ducted range hood at 40 L/s (144 m³/h)
Output
94.5 m³; 1.52 ACH
40 L/s satisfies the kitchen minimum, but in a large open-plan room it changes the air only one and a half times an hour, so a hood captures steam best when it is run on high while cooking.
Laundry with a vented dryer
Input
Laundry 2.4 x 1.8 x 2.4 m, exhaust 40 L/s
Output
10.4 m³; 13.9 ACH
A venting clothes dryer must also discharge to outdoor air under 10.8.2, and a room with a venting dryer needs make-up air in line with AS 1668.2.
Background and insight
ACH is a convenient way to compare rooms of different sizes, but it is not how every standard sets ventilation. ASHRAE 62.1 for commercial buildings gives outdoor air per person plus per square foot of floor, and ASHRAE 62.2 for homes uses 0.03 cfm per square foot of floor area plus 7.5 cfm for each occupant, counting bedrooms plus one. A 1,500 ft² three-bedroom house needs 75 cfm of continuous ventilation, which is only about 0.35 ACH.
Higher figures appear where airborne contaminants matter. In 2023 the CDC and NIOSH recommended aiming for 5 or more air changes per hour of clean air in occupied rooms, counting outdoor air, filtered return air and portable air cleaners together. Healthcare design under ASHRAE 170 sets 12 ACH for new airborne infection isolation rooms and 20 total ACH for operating rooms. Kitchens and bathrooms in homes get local exhaust under 62.2: a 100 cfm range hood or 5 ACH continuous for kitchens, and 50 cfm intermittent or 20 cfm continuous for bathrooms.
ACH50, measured with a blower door at 50 Pa, is a different number entirely. It describes airtightness under test pressure, not ventilation, and the 2021 IECC limits new homes to 3 ACH50 in most climate zones. Natural infiltration under normal conditions is a small fraction of the ACH50 value. With perfect mixing, each air change removes 63% of a contaminant, so 99% removal takes about 4.6 air changes.
Common use cases
Sizing portable air cleaners
Check whether a HEPA unit's CADR delivers 5 ACH in a classroom, office or bedroom, or how many units a large room needs.
Bathroom and kitchen fans
Turn a room volume into the fan cfm needed for a target number of air changes, then compare with the 62.2 minimums.
Whole-house ventilation
Get the ASHRAE 62.2 continuous rate for an ERV, HRV or exhaust-only system in a new or retrofitted home.
Workshops and spray booths
Estimate the extract airflow for a target ACH, then confirm against the solvent or dust guidance that applies.
Tips and limitations
- Rated flows on fan boxes are measured with no duct; long or flexible ducts and roof cowls lower the real flow, so allow a margin above 25 or 40 L/s.
- The ABCB condensation handbook shows a 20 mm undercut on a 700 mm wide door giving the 14,000 mm² make-up air opening.
- Discharging a fan into the roof space no longer complies; duct it to a wall or roof outlet.
Sources and further reading
- NCC 2025 Housing Provisions, Part 10.8 Condensation management, Australian Building Codes Board. 10.8.2 exhaust systems: 25 L/s and 40 L/s minimums, discharge to outdoor air, 10 minute run-on, make-up air of 14,000 mm² or to AS 1668.2.
- NCC 2025 Condensation in buildings handbook, Australian Building Codes Board
Frequently asked questions
What size exhaust fan does a bathroom need under the NCC?
At least 25 L/s for a bathroom or sanitary compartment (NCC Housing Provisions 10.8.2), which is 90 m³/h. Larger rooms or long duct runs justify a bigger fan so the room still clears quickly.
What flow rate does a kitchen range hood need?
40 L/s (144 m³/h) for a kitchen, discharging directly or through a duct to outdoor air. A recirculating hood that returns air to the room does not move air outdoors.
Does a bathroom fan need a run-on timer?
Yes, where the bathroom or toilet is not naturally ventilated as required by 10.6.2(a) and the fan does not run continuously. It must be interlocked with the light switch and keep running for 10 minutes after the light is turned off.
Can an exhaust fan vent into the roof space?
Not under the current Housing Provisions. Kitchen, range hood, bathroom, toilet and laundry exhaust must discharge directly, or via a shaft or duct, to outdoor air.
How many m³/h is 25 L/s?
90 m³/h. Multiply L/s by 3.6 to get m³/h, and divide m³/h by 3.6 to get L/s; 40 L/s is 144 m³/h.
Is there an in-depth guide to the Air Changes per Hour Calculator?
Yes. “Air Changes per Hour: What ACH Means and How Much Ventilation You Need” covers the background, how it works, common pitfalls and worked examples. Read the full guide.