Australia version. Sizes Australian copper tube by DN to AS 1432 Type B, in L/s and kPa, with the 3 m/s velocity cap from NCC Volume Three B1P2. US version
Water Pipe Size Calculator (Australia, AS 1432 Copper)
Size copper water services to AS 1432 Type B (DN15, DN18, DN20, DN25) from a flow in L/s, checked against the 3 m/s cap in the Plumbing Code of Australia.
The interactive tool loads here when JavaScript runs.
About this toolWhat is the Water Pipe Size Calculator?
Australian copper tube is ordered by DN, and the DN is a label rather than the bore. Under AS 1432 a DN15 tube is 12.70 mm outside, DN18 is 15.88 mm, DN20 is 19.05 mm and DN25 is 25.40 mm, so a Type B DN20 has a bore of only 17.01 mm. Using metric bores that match the label, or American tube tables, oversizes every pipe on paper. This version uses the Type B dimensions.
The Plumbing Code of Australia (NCC 2025 Volume Three, Performance Requirement B1P2) limits water velocity in cold water service pipework to 3 m/s for at least 99% of the time water is used in the peak hour. The deemed-to-satisfy route is to design to AS/NZS 3500.1, which sets the probable simultaneous flow for each section. Enter that flow in L/s, keep the velocity at or under 3 m/s, and check the pressure the run uses against the mains pressure at the meter.
- Minimum inside diameter from flow and maximum velocity
- Published inside diameters for copper L and M, PEX SDR 9, PVC and steel Schedule 40
- Actual velocity and Hazen-Williams friction loss with editable C
- Total loss over a length in psi, kPa and head
- Side-by-side comparison of every material for the same flow
Updated
How to use the Water Pipe Size Calculator
- Leave the units on SI and the tube standard on Australia (AS 1432 copper).
- Enter the probable simultaneous flow for the section in L/s, from the AS/NZS 3500.1 loading units or the fixture flow rates.
- Keep the maximum velocity at 3 m/s or lower; many designers aim well below the cap to reduce noise and water hammer.
- Add the run length plus an allowance for fittings and compare the kPa lost with the pressure available at the property.
Worked examples
DN15 fails the velocity cap at a shower and basin
Input
0.3 L/s through 20 m of Type B copper, 3 m/s limit
Output
DN15 would run at 3.23 m/s, so the calculator picks DN18 (13.84 mm bore): 1.99 m/s, 74.9 kPa lost
DN15 breaks the 3 m/s cap in B1P2. DN18 passes, but 75 kPa over 20 m is a large share of a typical mains supply, so a DN20 branch (1.32 m/s, 27.4 kPa) is often the better choice.
Main to the house at 0.6 L/s
Input
0.6 L/s, 25 m from the meter, 3 m/s limit, then a 2.2 m/s design target
Output
At 3 m/s: DN20, 2.64 m/s and 123.9 kPa lost. At 2.2 m/s: DN25 (22.96 mm bore), 1.45 m/s and 28.7 kPa
Sizing to the code cap alone would leave a DN20 main losing about 124 kPa before the water reaches the first tap. Going up to DN25 keeps most of the pressure for the fixtures.
Larger home or two dwellings, 1 L/s
Input
1.0 L/s, 30 m, 3 m/s limit
Output
Minimum bore 20.60 mm, DN25 Type B at 2.42 m/s, 88.8 kPa lost
Check whether a DN32 service is worth the cost. The friction loss falls steeply with every size step.
Background and insight
Nominal sizes are not inside diameters. Copper tube to ASTM B88 has an outside diameter 1/8 in larger than its nominal size, and type K, L and M differ only in wall thickness, so type M has the largest bore. PEX to ASTM F876 uses the same copper tube sizes (CTS) outside but a much thicker SDR 9 wall, so 3/4 in PEX has an inside diameter of only about 0.68 in. Schedule 40 PVC and steel pipe follow the iron pipe size system, where 3/4 in nominal has a 1.050 in OD and a 0.824 in ID.
Velocity limits protect against noise, water hammer and erosion of the pipe wall. The Copper Development Association and the Uniform Plumbing Code limit copper systems to 8 ft/s (2.4 m/s) for cold water and 5 ft/s (1.5 m/s) for hot water, and the CDA recommends 2 to 3 ft/s above 140 °F, where erosion corrosion is faster. Many designers keep residential branches nearer 4 ft/s for quiet.
Friction loss here uses the Hazen-Williams formula, an empirical fit for water at ordinary temperatures in turbulent flow. Its roughness constant C is about 150 for new plastic pipe, 140 for copper, 120 for new steel and 100 or less for old corroded steel. In US units, head loss per 100 ft = 0.2083 (100/C)^1.852 x gpm^1.852 / d^4.8655. Because loss scales with almost the fifth power of diameter, going up one pipe size typically cuts friction by more than half.
Common use cases
Residential water service and mains
Check that a service line or main carries the peak demand without exceeding the velocity limit or losing too much pressure.
Copper to PEX substitutions
See which PEX size matches the bore of an existing copper line before a repipe.
Hydronic and process loops
Pick a pipe size for a circulator flow at a target velocity, then read the head loss for pump selection.
Irrigation and outbuildings
Size a PVC run to a garden, barn or workshop and estimate the pressure left at the far end.
Tips and limitations
- Do not read DN as the bore: DN15 copper is 12.70 mm outside and about 10.9 mm inside in Type B.
- AS 1432 Type A tube has thicker walls than Type B, so its bore is a little smaller; check the type stamped on the tube.
- PE-X and polybutylene systems use their own sizes and insert fittings; size them from the maker's bore data.
- Each state administers plumbing through its own regulator and adopts the Plumbing Code of Australia with variations, so check local requirements before installing.
Sources and further reading
- NCC 2025 Volume Three, Part B1 Cold water services (B1P2 Velocity, B1D3), Australian Building Codes Board. The 3 m/s velocity performance requirement and the AS/NZS 3500.1 deemed-to-satisfy route.
- Copper tubing to AS 1432, Austral Wright Metals. Dimensions per AS 1432, as published by the maker: outside diameters and Type A to D wall thicknesses by size.
Frequently asked questions
What is the maximum water velocity allowed in Australia?
NCC 2025 Volume Three, Performance Requirement B1P2, says velocity in cold water service pipework must not exceed 3 m/s for no less than 99% of the time water is required during the peak hour.
What is the outside diameter of DN15 and DN20 copper?
Under AS 1432, DN15 is 12.70 mm and DN20 is 19.05 mm outside. Type B walls are 0.91 mm and 1.02 mm, giving bores of about 10.88 and 17.01 mm.
Is DN18 copper the same as 3/4 inch?
DN18 is 15.88 mm outside, which is 5/8 inch. DN20 is 19.05 mm, which is 3/4 inch. Australian copper sizes come from the old imperial outside diameters.
How do I find the design flow for a house?
AS/NZS 3500.1 converts the fixtures each section serves into a probable simultaneous flow. The calculator then sizes the pipe for that flow; it does not add up the loading units for you.
Does the 3 m/s limit apply to hot water too?
B1P2 covers cold water services. Heated water services are in Part B2 and AS/NZS 3500.4, and copper makers recommend lower speeds for hot water because erosion is faster at high temperatures.
Is there an in-depth guide to the Water Pipe Size Calculator?
Yes. “Water Pipe Sizing by Velocity and Hazen-Williams Friction Loss” covers the background, how it works, common pitfalls and worked examples. Read the full guide.