Three Phase Power Calculator (India, 415 V 50 Hz)

Find the current of a motor or load on a 415 V three phase or 240 V single phase, 50 Hz supply from HP, kW or kVA, with power factor and motor efficiency.

The interactive tool loads here when JavaScript runs.

About this tool

What is the Three-Phase Power Calculator?

Low-voltage supply to consumers in India is 415 V three phase and 240 V single phase at 50 Hz, the figures used in the BIS summary of distribution transformer standards and in CPWD specifications for switchboards. This version starts on 415 V and on a 5 HP motor, because pump sets and small motors are still bought by HP. A 5 HP motor at 84% efficiency and power factor 0.82 draws 7.53 A per phase.

Enter the current, kW, kVA, or the motor rating in HP or kW from its nameplate, with the power factor and efficiency. The tool shows the line current, the kW the motor takes from the supply, the kVA a DG set or transformer has to carry, and the kVAr that a capacitor would have to supply.

Every step is shown with your own numbers, so you can check the result against a hand calculation before it goes into a panel schedule or a load sanction application.

  • Single-phase and three-phase, line-to-line or line-to-neutral voltage
  • Solve from amps, kW, kVA or horsepower
  • Power factor, efficiency, kVAR and phase angle
  • Comparison table of current at other power factors
  • Formula panel with your numbers, copy and share
Read the guide: The Three-Phase Power Formula: Where √3 Comes From

Updated

How to use the Three-Phase Power Calculator

  1. Pick single-phase, three-phase with line-to-line voltage, or three-phase with line-to-neutral voltage.
  2. Enter the voltage. The preset buttons cover common systems such as 208, 400, 480 and 600 V line to line or 120, 230 and 277 V line to neutral.
  3. Choose what you know: current, kW, kVA or motor horsepower, and type the value.
  4. Enter the power factor (1 for resistive heaters, 0.8 to 0.9 for loaded induction motors) and, for motors, the nameplate efficiency.
  5. Read current, kW, kVA, kVAR and shaft output, and check the formula panel to see the numbers substituted.

Worked examples

5 HP pump on 415 V three phase

Input

3 phase 415 V, 5 HP, PF 0.82, efficiency 84%

Output

7.53 A per phase; 4.44 kW drawn, 5.41 kVA, 3.10 kVAr

Shaft output is 5 × 746 W = 3.73 kW, and the motor draws 3.73 ÷ 0.84 = 4.44 kW. Dividing 5.41 kVA by √3 × 415 V gives 7.53 A. Starting current is several times this, which is why starters and MCB curves are chosen from the motor maker's data.

15 kW motor in a small factory

Input

3 phase 415 V, motor rated output 15 kW, PF 0.85, efficiency 90%

Output

27.28 A per phase; 16.67 kW drawn, 19.61 kVA

Nameplates on IEC-frame motors give kW output. Pick "Motor rated output (kW)" so the efficiency is applied before the current is worked out.

1 HP single phase motor at 240 V

Input

Single phase 240 V, 1 HP, PF 0.8, efficiency 70%

Output

5.55 A; 1.07 kW drawn

Small single phase motors have lower efficiency and power factor than three phase ones, so their current is higher than a simple HP-to-watts conversion suggests.

What does a 50 kVA load draw?

Input

3 phase 415 V, 50 kVA, PF 0.9

Output

69.56 A per phase, 45 kW

Useful when matching a load to a DG set or a sanctioned load in kVA: the amps tell you the breaker and cable rating to start from.

Background and insight

For a balanced three-phase load the apparent power is S = √3 × V(LL) × I, where V(LL) is the line-to-line voltage and I the current in each line. The √3 comes from the 120° spacing of the phases: the voltage between two lines is √3 times the voltage from a line to neutral, and three phases each carry V(LN) × I, so S = 3 × V(LN) × I = √3 × V(LL) × I. Single-phase is simply S = V × I.

Real power, the part that does work and that a kWh meter bills, is P = S × PF. Reactive power, which circulates between the supply and the magnetic fields of motors and transformers, is Q = S × sin φ, where φ = arccos PF. Cables, breakers and transformers must carry the full current, so they are rated in amps or kVA, not kW. A 100 A load at 480 V and PF 0.85 is 83.1 kVA but only 70.7 kW.

Motor nameplates give output power in horsepower or kW at the shaft. The electrical input is the output divided by efficiency, so a 10 hp motor (7.457 kW) at 90% efficiency draws 8.29 kW from the supply. One horsepower is 745.7 W (NIST SP 811). For wiring and protection the NEC uses its own full-load current tables (430.248 for single-phase, 430.250 for three-phase) rather than nameplate amps, because they are deliberately conservative.

Common use cases

  • Feeder and breaker checks

    Convert a kW or kVA schedule into amps to choose cables, breakers and busbars.

  • Motor circuits

    Estimate the running current of a pump, fan or compressor from its horsepower, efficiency and power factor.

  • Generator and UPS loading

    Turn measured amps into kVA and kW to compare with a generator or UPS rating.

  • Reading meter data

    Make sense of a power analyser reading by relating amps, kW, kVA and kVAR.

Tips and limitations

  • Supply voltage varies through the day. Calculate at the nominal 415 V; if you measure a low voltage at the panel, the current of a constant-power load such as a motor rises in proportion.
  • For a motor, enter the nameplate efficiency and power factor. Leaving them at 100% and 1 would understate the current of the 5 HP example by about 31%.
  • Whether a premises gets a three phase connection depends on the load limits in your state's supply code, so check with the DISCOM before buying three phase equipment.
  • Wiring follows IS 732 and the CPWD General Specifications on government work; this tool gives the current those rules start from.

Sources and further reading

  1. Transformers: summary of Indian Standards (IS 1180 and others), Bureau of Indian Standards. End-user supply of 415 V, 3 phase (240 V, 1 phase), 50 Hz.
  2. General Specifications for Electrical Works, Part I: Internal (2013), Central Public Works Department, Government of India. Section 7: equipment for a 415 V, 3 phase, 50 Hz, 4 wire system; definitions per IS 732.
  3. NIST Special Publication 811, National Institute of Standards and Technology. Horsepower defined as 745.7 W.

Frequently asked questions

Is Indian three phase supply 415 V or 400 V?

Most Indian specifications and nameplates say 415 V three phase and 240 V single phase at 50 Hz. The BIS summary of its transformer standards gives the end-user supply as 415 V, 3 phase (240 V, 1 phase), 50 Hz, and CPWD switchboard specifications are written for a 415 V, 3 phase, 50 Hz, 4 wire system. You may also see 400/230 V on imported equipment; enter the voltage on your drawing.

How many amps does a 5 HP motor take on 415 V?

About 7.5 A per phase at 84% efficiency and power factor 0.82. A motor with a lower efficiency, or one running at part load where power factor drops, will draw more. Use the figures on your motor's nameplate.

How do I convert HP to kW?

One horsepower is 745.7 W, so 5 HP is 3.73 kW of shaft output. The electrical input is higher: divide by the motor efficiency. The calculator does both steps when you pick "Motor horsepower (hp)".

How do I find kVA from amps on 415 V?

kVA = √3 × 415 × amps ÷ 1,000, or 0.719 kVA per amp. So 100 A per phase is 71.9 kVA. Pick "Current (A)" and the tool also shows the kW and kVAr at your power factor.

Why does my motor draw more current than the calculation?

Low supply voltage, part load (which lowers power factor), an older motor with lower efficiency, or unbalanced phases. Measure all three phases with a clamp meter; if they differ, calculate each one separately at 240 V.

Can I use this to choose a cable or MCB?

It gives the full-load current to start from. Cable size then depends on the installation method, grouping, ambient temperature and voltage drop under IS 732 and the cable maker's tables. Have a licensed electrical contractor do the final design.