Canada version. Counts studs by the parallel-path method of NBC Section 9.36, checks the effective RSI against Table 9.36.2.6 and uses January 2.5% design temperatures from Appendix C. US version
Effective RSI and Heat Loss Calculator (Canada)
Work out the effective RSI of a 2x6 wall with studs counted the NBC way, check it against the Section 9.36 minimum for your degree-days and see the heat loss.
The interactive tool loads here when JavaScript runs.
About this toolWhat is the Heat Loss and U-Value Calculator?
Section 9.36 of the National Building Code of Canada sets minimum effective thermal resistance (RSI) for walls, ceilings and floors, and "effective" means the framing is counted. A 2x6 wall with RSI 3.34 batts (about R-19) between studs at 406 mm (16 in) on centre is not an RSI 3.34 wall: with the studs taking 23% of the area, the NBC worked example in Note A-9.36.2.4.(1) arrives at RSI 2.78, about R-15.8.
This version builds the wall the same way. Enter the stud cavity as a framed layer (stud depth, batt conductivity, framing percentage and stud conductivity), add the drywall, sheathing, siding and any exterior insulation, and the result gives the effective RSI and a pass or fail against the minimum you type. For walls, Table 9.36.2.6.-A asks for RSI 2.78 below 3,000 degree-days and 3.08 from 3,000 to 5,999 and 3.85 from 6,000 up, or 2.97 in zones 5 to 7A when the house has an HRV (Table 9.36.2.6.-B).
For the heat loss, NBC 9.33.5.1 sizes heating appliances by CSA F280 at an indoor 22 °C in living spaces (9.33.3.1) and the January 2.5% outdoor temperature for the location in Table C-2: -25 °C at Ottawa City Hall, -18 °C at Toronto City Hall, -30 °C in Calgary and -33 °C in Winnipeg.
- Up to ten layers by thickness and conductivity or by known R-value
- ISO 6946 and ASHRAE surface resistances for walls, roofs and floors
- R-value and U-value in both SI and US units at once
- Heat loss in watts and BTU/h, plus seasonal kWh and therms from degree-days
- Layer share table and steady-state interface temperatures
Updated
How to use the Heat Loss and U-Value Calculator
- Keep the units on metric (RSI). List the layers from the inside: drywall, the framed cavity, sheathing, exterior insulation, siding.
- For the stud cavity choose "Framed cavity" and enter the stud depth (89 or 140 mm), the batt conductivity, the framing share (23% at 406 mm, 20% at 610 mm for typical walls) and the stud conductivity.
- Pick the NBC wall air films (0.12 inside, 0.03 outside).
- Type the minimum effective RSI from Table 9.36.2.6.-A or -B for your heating degree-days.
- Enter 22 °C inside, the January 2.5% temperature from Table C-2 and the degree-days below 18 °C for a seasonal estimate.
Worked examples
The NBC example wall in Ottawa
Input
Gypsum 0.08, 38 x 140 mm studs at 406 mm (23%) with RSI 3.34 batts, gypsum sheathing 0.08, metal siding 0.11, NBC films; 30 m², 22 °C to -25 °C, 4,440 degree-days
Output
Framed layer RSI 2.36; effective RSI 2.78 (R-15.8), U 0.360; 507 W; about 1,150 kWh a year; fails RSI 3.08
Ottawa City Hall has 4,440 degree-days, which is zone 6. Without an HRV the wall needs RSI 3.08 and with one 2.97, so it falls short either way; as built it would comply only in zone 4, below 3,000 degree-days.
Studs at 24 in with exterior foam
Input
Same wall with studs at 610 mm (20% framing), 11 mm plywood sheathing (k 0.13) and 38 mm XPS (k 0.033) outside
Output
Effective RSI 4.03 (R-22.9), U 0.248; 350 W at -25 °C; meets 3.08
Wider stud spacing and a continuous layer of exterior insulation both cut the bridging. The foam alone adds about RSI 1.15 because nothing interrupts it.
What the clear-field number hides
Input
The example wall with the batt entered as a plain RSI 3.34 layer (no studs)
Output
RSI 3.76 instead of 2.78
Ignoring the studs overstates this wall by about a third, enough to turn a fail into a pass. NBC 9.36.2.4 requires the effective value, so always enter the cavity as a framed layer.
Background and insight
The method is the one in ISO 6946 and the ASHRAE Handbook of Fundamentals: thermal resistances of layers that the heat crosses one after another simply add, R = d / k for each homogeneous layer, and U is the reciprocal of the total. Surface resistances account for the thin film of still air on each face. ISO 6946 uses 0.13 m²·K/W inside for walls, 0.10 for heat flowing up through a roof or ceiling, 0.17 for heat flowing down through a floor, and 0.04 outside. ASHRAE tabulates the same idea in US units: R-0.68 for still air on a vertical surface and R-0.17 for a 15 mph winter wind.
US and SI R-values describe the same property in different units, which is why a product sold as R-13 in the United States is RSI 2.29 elsewhere. One m²·K/W equals 5.678 ft²·°F·h/BTU. Conductivities in the material list are typical design values from ISO 10456, CIBSE Guide A and manufacturer literature; insulation products vary with density and age, so the declared lambda value on the datasheet should replace the default whenever you have it.
A clear-field calculation like this ignores thermal bridges. In a timber stud wall the studs occupy roughly 15 to 25% of the area and conduct three times better than mineral wool, so the whole-wall U-value is noticeably worse than the clear-field one. Steel studs are far worse again. Full heat-load methods (ACCA Manual J, EN 12831) add bridging, ventilation and infiltration on top of the fabric losses calculated here.
Common use cases
Comparing insulation upgrades
See how much an extra 50 mm of PIR board or a thicker batt changes the U-value and the seasonal kWh before pricing the work.
Building regulations checks
Check that a proposed wall or roof meets a target U-value such as 0.18 or 0.26 W/m²·K, then confirm with a full ISO 6946 calculation including bridging.
Sizing a room heater
Add up the fabric losses of each wall, ceiling and floor to get a first estimate of the heat a room needs at the design outdoor temperature.
Condensation screening
Use the interface temperatures to see where a wall drops below the indoor dew point and where a vapour control layer belongs.
Tips and limitations
- R-values on batt packaging are imperial; divide by 5.678 for RSI (R-20 is RSI 3.52).
- Section 9.36 states its requirements in RSI; R-values are given for information only (Note A-9.36.1.2.(3)).
- An attached garage or enclosed porch on the other side of a wall lets you reduce that wall's required effective RSI by 0.16 (Sentence 9.36.2.4.(4)).
Sources and further reading
- National Building Code of Canada 2025, National Research Council Canada. NRC Publications Archive (free PDF). Division B: Tables 9.36.2.6.-A and -B, Note A-9.36.2.4.(1) (effective RSI example, framing percentages, air films), 9.33.3.1, 9.33.5.1, Sentence 1.1.3.1.(3) and Appendix C, Table C-2.
- National Building Code of Canada 2025 (catalogue record), Government of Canada Publications
Frequently asked questions
What is effective RSI?
It is the thermal resistance of the whole assembly with the framing counted, plus the air films. The NBC method adds the continuous layers and treats the stud and batt layer as two parallel paths weighted by their areas, as in Note A-9.36.2.4.(1).
What RSI does an above-ground wall need under the NBC?
In NBC 2025, without an HRV (Table 9.36.2.6.-A): 2.78 below 3,000 degree-days, 3.08 from 3,000 to 5,999 (zones 5 to 7A) and 3.85 from 6,000 up (zones 7B and 8). With an HRV meeting 9.36.3.9 (Table 9.36.2.6.-B): 2.78, then 2.97 for zones 5 to 7A and 3.08 for zones 7B and 8. Most provinces still enforce an earlier edition, so check the one adopted where you build.
What RSI does an attic ceiling need?
Ceilings below attics need RSI 6.91 in zone 4, 8.67 in zones 5 and 6 and 10.43 in zones 7A to 8 without an HRV. With an HRV, zone 5 drops to 6.91 and zone 7A to 8.67.
Which outdoor temperature should I use for a heat loss in Canada?
The January 2.5% design temperature for your location in NBC Appendix C, Table C-2, unless your authority having jurisdiction sets its own (Sentence 1.1.3.1.(3)). Note A-1.1.3.1.(3) calls the 2.5% values the least restrictive that can be used; a designer may choose the colder 1% value.
Is this a CSA F280 heat loss?
No. F280 adds up every wall, window, ceiling, floor, foundation and air leakage for each room. This tool gives the effective RSI and heat loss of one assembly, which is one line of that calculation and a quick way to compare wall options.
How do I convert RSI to R-value?
Multiply RSI by 5.678. RSI 3.08 is R-17.5 and RSI 2.78 is R-15.8.
Is there an in-depth guide to the Heat Loss and U-Value Calculator?
Yes. “U-Value, R-Value and Heat Loss: Calculating a Wall Layer by Layer” covers the background, how it works, common pitfalls and worked examples. Read the full guide.