Canada version. Checks against NBC Part 9 Table 9.4.3.1 (live load only) instead of the US IBC table, with a 2x10 SPF floor joist example in feet and inches. US version

Beam Deflection Calculator (Canada)

Joist and beam deflection checked against Part 9 of the National Building Code of Canada: L/360 for floors, L/240 and L/180 for roofs, under live load only.

The interactive tool loads here when JavaScript runs.

About this tool

What is the Beam Deflection Calculator?

Houses and small buildings in Canada follow Part 9 of the National Building Code, as adopted by each province, and its Table 9.4.3.1 sets the maximum deflection of structural members as a fraction of the clear span: L/360 for floor beams, joists and decking in all cases, L/360 for roof and ceiling members carrying plaster or gypsum board, L/240 with other ceilings and L/180 with no ceiling. Sentence 9.4.3.1.(2) says dead loads need not be counted, so the check is under live load. Choose NBC Part 9 in "Deflection limits from" to use these rows.

The numbers look like the US IBC limits, but they apply differently: the IBC row of L/240 is a total-load check on floors, while in Part 9 every floor is L/360 under live load alone. This version starts with a 2x10 SPF joist (1.5 x 9.25 in) at 16 in on centre spanning 14 ft, with a 40 psf live load, or 53.3 lb per foot of joist. It deflects 0.33 in, L/505, well inside L/360.

The same span in 2x8 deflects 0.69 in, L/243, which fails L/360 by almost half. Deflection rises with the cube of the depth lost, which is why span tables jump so much between joist sizes. For an actual house, use the span tables in your provincial code or an engineered design, which also account for vibration.

  • Seven standard support and load cases, including an off-centre point load
  • Maximum deflection, its location, both end slopes, reactions and peak moment
  • Deflection limit checks with utilisation from IBC Table 1604.3, the UK NA to BS EN 1993-1-1, IS 800 / IS 456 or NBC Part 9, plus optional bending stress from S
  • Typical E presets for steel, stainless, aluminium, timber grades, glulam and concrete
  • SI and US units with conversion in place, deflected-shape chart, copy and share link
Read the guide: Beam Deflection Formulas: Where 5wL⁴/384EI Comes From and When L/360 Applies

Updated

How to use the Beam Deflection Calculator

  1. Choose SI or US units. The force unit can be kN or N, or kip or lbf; switching systems converts the numbers you already typed.
  2. Pick the support and load case. For an off-centre point load, enter its distance a from the left support.
  3. Enter the span and the load. For a uniform load include the beam's self-weight and any dead load, not only the live load.
  4. Pick a material to fill in a typical E, or type your own, then enter the second moment of area I about the bending axis. Add the section modulus S if you also want the bending stress.
  5. Read the maximum deflection, its position, the end slopes and the moment, then check the L/180, L/240 and L/360 table and the deflected-shape chart.

Worked examples

2x10 SPF floor joist, 14 ft, 16 in o.c.

Input

Simply supported, 14 ft, 53.3 lb/ft, E 1,400 ksi, I 98.93 in⁴, NBC Part 9 limits

Output

0.333 in (L/505); L/360 allows 0.467 in, so 71% used

53.3 lb/ft is a 40 psf live load on 16 in spacing. Dead load is left out, as Sentence 9.4.3.1.(2) allows.

2x8 SPF at the same span

Input

Simply supported, 14 ft, 53.3 lb/ft, E 1,400 ksi, I 47.63 in⁴

Output

0.691 in (L/243); exceeds L/360 at 148%

It would pass the L/240 ceiling limit for a roof joist, but floors are L/360 in every case.

2x10 SPF stretched to 16 ft

Input

Simply supported, 16 ft, 53.3 lb/ft, E 1,400 ksi, I 98.93 in⁴

Output

0.568 in (L/338); exceeds L/360 at 106%

Two more feet of span add 70% to the deflection; 12 in spacing or a deeper joist brings it back.

Background and insight

All of these formulas come from integrating the Euler-Bernoulli beam equation, E I y'' = M(x), twice and fixing the constants with the support conditions. That gives the familiar coefficients: 5/384 for a simply supported uniform load, 1/48 for a central point load, 1/3 and 1/8 for cantilevers, and 1/384 and 1/192 for fully fixed ends. The theory assumes a straight, prismatic beam of linear-elastic material, small deflections, and plane sections that stay plane; shear deformation is ignored, which is accurate for spans more than about ten times the depth.

Deflection depends on the product E I, the flexural stiffness. E is a material constant (about 200 GPa or 29,000 ksi for any structural steel, whatever its strength grade) and I depends only on the shape of the cross-section. That is why a higher-strength steel does nothing for deflection and why doubling a beam's depth cuts deflection by a factor of eight. Timber E values in the presets are mean values: EN 338 lists 11 GPa for C24 and 8 GPa for C16, and the NDS Supplement gives 1,600,000 psi for Douglas fir-larch No.2 and 1,400,000 psi for spruce-pine-fir No.2.

The limits come from the International Building Code, Table 1604.3: L/360 for floor live load, L/240 for floors under total load and for roofs with a plaster ceiling, and L/180 for roofs without a ceiling. Eurocode practice is similar, with L/250 for quasi-permanent load and L/300 or stricter where finishes can crack.

Common use cases

  • Sizing floor joists and beams

    Check that a timber joist, steel beam or glulam meets L/360 under live load before ordering material.

  • Shelves, mezzanines and racks

    Estimate how far a shelf or platform beam will sag with a known load so it looks and feels solid.

  • Cantilevered brackets and canopies

    Get the tip deflection and slope of a bracket, sign arm or balcony beam under a point or uniform load.

  • Machine frames and test rigs

    Keep aluminium or steel frame members stiff enough for alignment-sensitive equipment.

  • Checking hand calculations

    Students and engineers can confirm a textbook answer and see the full deflected shape.

Tips and limitations

  • The joist moment of inertia is b x d³ / 12 with actual sizes: a 2x10 is 1.5 x 9.25 in (38 x 235 mm).
  • The preset E of 1,400 ksi is a typical softwood value; take the modulus for your species and grade from CSA O86 or the supplier and edit it.
  • Use live load only for the Part 9 check; for Part 4 (engineered) designs, follow the design standard for the material.

Sources and further reading

  1. British Columbia Building Code 2018, Division B, Section 9.4: Structural requirements, Province of British Columbia. Article 9.4.3.1 and Table 9.4.3.1, maximum deflections, including L/240 for decks and balconies serving a single dwelling unit.
  2. National Building Code of Canada, National Research Council Canada (Government of Canada Publications). Part 9, housing and small buildings.

Frequently asked questions

What is the deflection limit for floor joists in Canada?

L/360 under live load for floor beams, joists and decking in all cases, under Table 9.4.3.1 of the National Building Code. Many provinces adopt it unchanged; check your provincial code edition.

Is dead load included in the Part 9 deflection check?

No. Sentence 9.4.3.1.(2) says dead loads need not be considered in computing these deflections, so enter the live load only.

What deflection limit applies to rafters?

L/180 where there is no ceiling, L/240 where the ceiling is something other than plaster or gypsum board, and L/360 with a plaster or gypsum board ceiling.

What are the deflection limits for a deck?

Table 9.4.3.1 allows L/240 for beams, joists and decking of balconies, decks and other accessible exterior platforms serving a single dwelling unit, and L/360 in other cases.

How do I find I for a 2x10?

Use the actual size, 1.5 x 9.25 in: I = 1.5 x 9.25³ / 12 = 98.93 in⁴. A 2x8 (1.5 x 7.25 in) is 47.63 in⁴ and a 2x12 (1.5 x 11.25 in) 178 in⁴.

Is there an in-depth guide to the Beam Deflection Calculator?

Yes. “Beam Deflection Formulas: Where 5wL⁴/384EI Comes From and When L/360 Applies” covers the background, how it works, common pitfalls and worked examples. Read the full guide.