Three-Phase Power Calculator (Canada, 600 V and 208 V)

Convert amps, kW, kVA and motor horsepower on 347/600 V, 120/208 V or 120/240 V, 60 Hz Canadian services, with line-to-line or line-to-neutral voltage.

The interactive tool loads here when JavaScript runs.

About this tool

What is the Three-Phase Power Calculator?

BC Hydro's standard services, for example, are 347/600 V and 120/208 V three-phase and 120/240 V single-phase, and Canadian systems run at 60 Hz. The 600 V system is the one US-based calculators tend to leave out, so this version starts there. A 10 hp motor at 91% efficiency and power factor 0.85 draws 9.28 A per line at 600 V, a third of what the same motor takes at 208 V.

Choose line to line (600 V or 208 V) or line to neutral (347 V or 120 V) to match the drawing, then enter amps, kW, kVA or horsepower. Motor nameplates may give hp or kW, and the federal efficiency rules state both, so the tool takes either.

The results show the current, real and apparent power and kVAR, and the working shows each step so you can put it in a load calculation or a submission to the inspection authority.

  • Single-phase and three-phase, line-to-line or line-to-neutral voltage
  • Solve from amps, kW, kVA or horsepower
  • Power factor, efficiency, kVAR and phase angle
  • Comparison table of current at other power factors
  • Formula panel with your numbers, copy and share
Read the guide: The Three-Phase Power Formula: Where √3 Comes From

Updated

How to use the Three-Phase Power Calculator

  1. Pick single-phase, three-phase with line-to-line voltage, or three-phase with line-to-neutral voltage.
  2. Enter the voltage. The preset buttons cover common systems such as 208, 400, 480 and 600 V line to line or 120, 230 and 277 V line to neutral.
  3. Choose what you know: current, kW, kVA or motor horsepower, and type the value.
  4. Enter the power factor (1 for resistive heaters, 0.8 to 0.9 for loaded induction motors) and, for motors, the nameplate efficiency.
  5. Read current, kW, kVA, kVAR and shaft output, and check the formula panel to see the numbers substituted.

Worked examples

10 hp motor on a 600 V service

Input

3-phase 600 V line to line, 10 hp, PF 0.85, efficiency 91%

Output

9.28 A per line; 8.19 kW drawn, 9.64 kVA

If the nameplate gives 575 V, enter that instead: the current rises to 9.68 A. Size the branch circuit from the nameplate and the code tables under Section 28 of the Canadian Electrical Code, not from this running estimate.

Same 30 kW load at 208 V and at 600 V

Input

3-phase, 30 kW, PF 0.95; 208 V then 600 V

Output

87.65 A per line at 208 V; 30.39 A per line at 600 V

This is why larger buildings take a 347/600 V service and step down to 120/208 V only for receptacles and small loads: the 600 V feeders carry about a third of the current.

347 V line-to-neutral reading

Input

3-phase, 347 V line to neutral, 100 A, PF 0.9

Output

104.1 kVA, 93.69 kW; 601 V line to line

Entering 347 V with the line-to-neutral option gives the same kVA as 600 V line to line, as it should.

48 A EV charger on 240 V or 208 V

Input

Single-phase, 48 A, PF 1; 240 V then 208 V

Output

11.52 kW at 240 V; 9.98 kW at 208 V

In a building with a 120/208 V service, a charger connected between two phases sees 208 V, not 240 V, and delivers about 13% less power for the same current.

Background and insight

For a balanced three-phase load the apparent power is S = √3 × V(LL) × I, where V(LL) is the line-to-line voltage and I the current in each line. The √3 comes from the 120° spacing of the phases: the voltage between two lines is √3 times the voltage from a line to neutral, and three phases each carry V(LN) × I, so S = 3 × V(LN) × I = √3 × V(LL) × I. Single-phase is simply S = V × I.

Real power, the part that does work and that a kWh meter bills, is P = S × PF. Reactive power, which circulates between the supply and the magnetic fields of motors and transformers, is Q = S × sin φ, where φ = arccos PF. Cables, breakers and transformers must carry the full current, so they are rated in amps or kVA, not kW. A 100 A load at 480 V and PF 0.85 is 83.1 kVA but only 70.7 kW.

Motor nameplates give output power in horsepower or kW at the shaft. The electrical input is the output divided by efficiency, so a 10 hp motor (7.457 kW) at 90% efficiency draws 8.29 kW from the supply. One horsepower is 745.7 W (NIST SP 811). For wiring and protection the NEC uses its own full-load current tables (430.248 for single-phase, 430.250 for three-phase) rather than nameplate amps, because they are deliberately conservative.

Common use cases

  • Feeder and breaker checks

    Convert a kW or kVA schedule into amps to choose cables, breakers and busbars.

  • Motor circuits

    Estimate the running current of a pump, fan or compressor from its horsepower, efficiency and power factor.

  • Generator and UPS loading

    Turn measured amps into kVA and kW to compare with a generator or UPS rating.

  • Reading meter data

    Make sense of a power analyser reading by relating amps, kW, kVA and kVAR.

Tips and limitations

  • Canadian services are 60 Hz. The power formulas here do not depend on frequency, but motor speed and capacitor sizing do.
  • Services at 277/480 V and 600 V delta exist, but BC Hydro lists them as non-standard, needing customer-supplied transformers. Check your utility's conditions of service for what it offers.
  • Use the line-to-neutral option for 347 V or 120 V circuits and line to line for 600 V or 208 V, never a mix of the two.
  • For unbalanced loads, work out each phase at 347 V or 120 V on its own and add the powers.

Sources and further reading

  1. Electric motors (1 to 500 HP/0.746 to 375 kW), Natural Resources Canada. Scope of the federal motor efficiency rules: up to 600 V AC, 50 or 60 Hz.
  2. Electrical service voltages, BC Hydro. Standard secondary services: 120/240 V, 120/208 V and 347/600 V.
  3. CSA C22.1:24, Canadian Electrical Code, Part I, Standards Council of Canada (catalogue entry for CSA C22.1:24)

Frequently asked questions

What three-phase voltages are used in Canada?

The standard secondary services BC Hydro lists are 120/240 V single-phase, three-wire, and 120/208 V and 347/600 V wye, three-phase, four-wire. Other utilities offer similar services; check their conditions of service.

How many amps does a 10 hp motor draw at 600 V?

About 9.3 A per line with 91% efficiency and power factor 0.85, or 9.7 A at a 575 V nameplate voltage. For wiring and protection, use the nameplate current and Section 28 of the Canadian Electrical Code as adopted in your province.

Why do Canadian buildings use 347 V lighting?

On a 347/600 V wye service, 347 V is the line-to-neutral voltage, so lighting can run directly from the 600 V system without a step-down transformer. The calculator handles it with the line-to-neutral option.

Do motor efficiency rules apply in Canada?

Yes. Natural Resources Canada regulates electric motors from 1 to 500 hp (0.746 to 375 kW) with a nominal voltage of not more than 600 V AC, under the Energy Efficiency Regulations, 2016. Efficiency levels follow NEMA MG-1 Table 12-12 for most motors made on or after June 1, 2016.

Is 208 V the same as 240 V for a heater or charger?

No. A resistive load rated at 240 V gives about 75% of its rated power at 208 V, because power falls with the square of voltage. A charger set to the same current gives 13% less power.

Can I size a conductor from this result?

It gives the load current to start from. Conductor ampacity, motor branch circuits and overcurrent protection follow the Canadian Electrical Code, Part I (CSA C22.1) as adopted by your province, and the work needs a licensed electrician and a permit.

Is there an in-depth guide to the Three-Phase Power Calculator?

Yes. “The Three-Phase Power Formula: Where √3 Comes From” covers the background, how it works, common pitfalls and worked examples. Read the full guide.