Transformer Sizing Calculator (Canada, 600 V)
Size a 600 V to 120/208 V or 120/240 V dry-type transformer from kW, kVA or amps, pick the next standard kVA and see 60 Hz full-load currents on both sides.
The interactive tool loads here when JavaScript runs.
About this toolWhat is the Transformer Sizing Calculator?
Buildings on a 347/600 V service feed their receptacles and small loads through dry-type transformers that step 600 V down to 120/208 V, so that is where this version starts. A 60 kW receptacle and equipment load at power factor 0.9 with 20% spare needs 80 kVA, which rounds up to a 112.5 kVA unit carrying 108 A on the 600 V side and 312 A at 208 V.
Enter the load as kW with a power factor, as kVA, or as measured secondary amps. The calculator adds your growth margin, picks the next standard rating from the North American list and shows primary and secondary full-load currents and the voltage ratio.
Dry-type transformers from 15 kVA up, at 60 Hz, have to meet federal minimum efficiency levels, so the rating you choose also decides which efficiency table the unit is built to.
- Load from kW and PF, kVA or amps
- Spare capacity and next standard rating (ANSI or IEC lists)
- Primary and secondary full-load and actual load currents
- Voltage (turns) ratio
- Comparison table of neighbouring sizes
Updated
How to use the Transformer Sizing Calculator
- Choose single-phase or three-phase.
- Enter the load as kW with power factor, as kVA, or as amps at the secondary voltage.
- Set the spare capacity you want, for example 20% for growth.
- Enter the primary and secondary voltages (line to line for three-phase) and choose North American or IEC ratings.
- Read the standard size, how heavily it is loaded today, the full-load currents and the voltage ratio.
Worked examples
600 V to 120/208 V for a tenant floor
Input
Three-phase, 60 kW at PF 0.9, 20% spare, 600 V to 208 V, North American ratings
Output
66.7 kVA load, 80 kVA required, 112.5 kVA (59% loaded); 108.3 A at 600 V, 312.3 A at 208 V
A 75 kVA unit would be just short of the 80 kVA needed. The table under the result shows how loaded each neighbouring size would be.
Single-phase 600 V to 120/240 V
Input
Single-phase, 30 kVA, 20% spare, 600 V to 240 V
Output
36 kVA required, 37.5 kVA (80% loaded); 62.5 A at 600 V, 156.3 A at 240 V
Common for a shop panel or a single-phase load in a building with only a 600 V service.
Utility-supplied 25 kV service to 600 V
Input
Three-phase, 1,200 kVA, 20% spare, 24,940 V to 600 V
Output
1,440 kVA required, 1,500 kVA (80% loaded); 34.7 A at 24.94 kV, 1,443.4 A at 600 V
Primary voltages depend on the utility; BC Hydro's standard primary services include 14,400/24,940 V and 7,200/12,470 V wye.
Background and insight
Transformers are rated in kVA rather than kW because their heating depends on current and voltage, not on the power factor of the load. Full-load current is I = kVA × 1000 ÷ V for single-phase and I = kVA × 1000 ÷ (√3 × V(LL)) for three-phase. A 75 kVA three-phase unit stepping 480 V down to 208Y/120 V carries 90.2 A on the primary and 208.2 A on the secondary.
The load figure should be the calculated demand, after any diversity your code allows, not the sum of nameplates. Designers then add spare capacity, commonly 20 to 25%, so that the unit runs at about 80% of its rating today. That margin covers growth, keeps losses and temperature rise down, and leaves room for motor starting. Harmonic-rich loads (computers, drives, LED drivers) may need a K-factor rated transformer or a further derating.
For an ideal transformer the voltage ratio equals the turns ratio, a = Vp ÷ Vs = Np ÷ Ns, and current goes the other way: Is = Ip × a. In three-phase units the per-winding ratio depends on the connection; a delta-wye 480 to 208Y/120 V transformer has 480 V on each delta winding and 120 V on each wye winding, a winding ratio of 4:1, even though the line-to-line ratio is 2.31:1. Ratings follow ANSI/IEEE C57.12 series standards in North America and IEC 60076 elsewhere; protection follows NEC 450.3 or your local code.
Common use cases
Specifying a step-down transformer
Choose the kVA for a 480 to 208/120 V panel feeding receptacles and lighting.
Machine isolation transformers
Size a control or isolation transformer for imported equipment that needs a different voltage.
Checking an existing unit
See how loaded a transformer is by entering the measured secondary amps.
Planning protection
Get primary and secondary full-load amps as the starting point for breakers and conductors.
Tips and limitations
- Check that the dry-type unit is listed as meeting CSA C802.2 efficiency levels; the federal regulations cover single-phase units from 15 to 833 kVA and three-phase units from 15 to 7,500 kVA at 60 Hz with a high-voltage winding of 35 kV or less.
- Use the demand load calculated under the Canadian Electrical Code for the load figure, not the sum of nameplates.
- Delta-wye 600 V to 120/208 V units have 600 V on each delta winding and 120 V on each wye winding, a winding ratio of 5:1, although the line-to-line ratio is 2.88:1.
- Harmonic-rich loads, such as many computers or LED drivers, may call for a K-rated transformer or a larger size.
Sources and further reading
- Energy Efficiency Regulations, 2016 (SOR/2016-311), section 703: dry-type transformer, Justice Laws Website, Government of Canada. Definition and scope (15 to 833 kVA single-phase, 15 to 7,500 kVA three-phase, 60 Hz, 35 kV or less) and CSA C802.2.
- Electrical service voltages, BC Hydro. Standard secondary and primary service voltages.
- CSA C22.1:24, Canadian Electrical Code, Part I, Standards Council of Canada (catalogue entry for CSA C22.1:24)
Frequently asked questions
What size transformer do I need to go from 600 V to 208 V?
Work out the demand load in kVA, add 20 to 25% for growth and pick the next standard size: 15, 30, 45, 75, 112.5, 150, 225 or 300 kVA are the common three-phase dry-type ratings. A 60 kW load at PF 0.9 with 20% spare needs 112.5 kVA.
How many amps is a 75 kVA transformer at 600 V?
75,000 ÷ (√3 × 600) = 72.2 A on the 600 V side and 208.2 A at 208 V.
Do dry-type transformers have to meet efficiency rules in Canada?
Yes. The Energy Efficiency Regulations, 2016 define a dry-type transformer as single-phase from 15 to 833 kVA or three-phase from 15 to 7,500 kVA, at 60 Hz, with a high-voltage winding of 35 kV or less, and set minimum efficiency by reference to CSA C802.2. Autotransformers, drive, welding and several other types are excluded.
Why is the voltage ratio 2.88 and not 5?
600 ÷ 208 = 2.88 is the line-to-line ratio. In a delta-wye unit each primary winding sees 600 V and each secondary winding 120 V, so the turns ratio of the windings is 5:1.
Which rules cover transformer protection in Canada?
The Canadian Electrical Code, Part I (CSA C22.1), as adopted with amendments by each province and territory. Your provincial inspection authority may publish bulletins on how it applies.
Is there an in-depth guide to the Transformer Sizing Calculator?
Yes. “Transformer Sizing: kVA, Full-Load Amps and Standard Ratings” covers the background, how it works, common pitfalls and worked examples. Read the full guide.