Canada version. Works in L/s, m/s and kPa as the National Plumbing Code of Canada does, with copper and PEX in NPS sizes and the NPC 2025 rules for houses. US version

Water Pipe Size Calculator (Canada, National Plumbing Code)

Size a water service or distribution pipe in NPS copper or PEX from a flow in L/s, with velocity in m/s and loss in kPa, checked against the National Plumbing Code.

The interactive tool loads here when JavaScript runs.

About this tool

What is the Water Pipe Size Calculator?

Canadian plumbing mixes two systems: the National Plumbing Code is written in SI (L/s, m/s, kPa), while pipe and tube are still sold by nominal pipe size, NPS ½, ¾ and 1. This version starts in SI and picks from the same ASTM copper and PEX CTS tables Canadian suppliers stock, so the answer reads the way an inspector expects.

NPC 2025 asks for water systems that deliver peak demand at the flow pressures the fixture makers specify (Sentence 2.6.3.1.(1)) and sets the water service at no less than NPS ¾ (2.6.3.4.(1)). Maximum velocities are those the pipe and fitting manufacturer recommends (2.6.3.5.(1)). For one- and two-unit houses, Table 2.6.3.4 offers a shortcut sized at 3.0, 2.4 or 1.5 m/s, but only where the pressure at the building entry is at least 200 kPa and the whole system is no longer than 90 m (Sentence 2.6.3.4.(5)). The calculator lets you test a run outside those limits. Most provinces still enforce an earlier edition; check the one adopted where you build.

  • Minimum inside diameter from flow and maximum velocity
  • Published inside diameters for copper L and M, PEX SDR 9, PVC and steel Schedule 40
  • Actual velocity and Hazen-Williams friction loss with editable C
  • Total loss over a length in psi, kPa and head
  • Side-by-side comparison of every material for the same flow
Read the guide: Water Pipe Sizing by Velocity and Hazen-Williams Friction Loss

Updated

How to use the Water Pipe Size Calculator

  1. Keep SI units and the US / Canada tube standard.
  2. Enter the peak demand in L/s. A shower draws about 0.13 L/s (2 US gpm); the code's fixture units give the total.
  3. Enter the maximum velocity from the pipe or fitting maker; 2.4 m/s for cold copper and 1.5 m/s for hot match the columns in Table 2.6.3.4.
  4. Enter the developed length and read the kPa lost, then compare it with the street pressure less the rise to the highest fixture.

Worked examples

Water service for a detached house

Input

0.6 L/s, 30 m, copper type L, 2.4 m/s, then 1.5 m/s

Output

¾ in at 1.92 m/s and 68.6 kPa lost; at 1.5 m/s the size goes to 1 in, 1.13 m/s and 18.7 kPa

NPS ¾ is the smallest service the code allows, and it passes at 2.4 m/s. On a lot with only 200 kPa at the entry, though, a third of the pressure is gone before the first fixture, so 1 in is worth it on a long service.

PEX instead of copper for the same service

Input

0.6 L/s, 30 m, PEX SDR 9, C 150, 2.4 m/s

Output

1 in PEX (0.875 in bore): 1.55 m/s, 35.6 kPa lost

¾ in PEX has a 0.681 in bore, too small for 0.6 L/s at 2.4 m/s, so PEX goes up a size where copper did not.

Hot water branch at 1.5 m/s

Input

0.3 L/s, 15 m, copper type M

Output

¾ in type M (0.811 in bore): 0.90 m/s, 8.1 kPa

Type L would allow ⅝ in at 1.33 m/s, but ⅝ in is uncommon in house distribution, and the larger tube keeps hot water velocity well under the limit makers recommend.

Background and insight

Nominal sizes are not inside diameters. Copper tube to ASTM B88 has an outside diameter 1/8 in larger than its nominal size, and type K, L and M differ only in wall thickness, so type M has the largest bore. PEX to ASTM F876 uses the same copper tube sizes (CTS) outside but a much thicker SDR 9 wall, so 3/4 in PEX has an inside diameter of only about 0.68 in. Schedule 40 PVC and steel pipe follow the iron pipe size system, where 3/4 in nominal has a 1.050 in OD and a 0.824 in ID.

Velocity limits protect against noise, water hammer and erosion of the pipe wall. The Copper Development Association and the Uniform Plumbing Code limit copper systems to 8 ft/s (2.4 m/s) for cold water and 5 ft/s (1.5 m/s) for hot water, and the CDA recommends 2 to 3 ft/s above 140 °F, where erosion corrosion is faster. Many designers keep residential branches nearer 4 ft/s for quiet.

Friction loss here uses the Hazen-Williams formula, an empirical fit for water at ordinary temperatures in turbulent flow. Its roughness constant C is about 150 for new plastic pipe, 140 for copper, 120 for new steel and 100 or less for old corroded steel. In US units, head loss per 100 ft = 0.2083 (100/C)^1.852 x gpm^1.852 / d^4.8655. Because loss scales with almost the fifth power of diameter, going up one pipe size typically cuts friction by more than half.

Common use cases

  • Residential water service and mains

    Check that a service line or main carries the peak demand without exceeding the velocity limit or losing too much pressure.

  • Copper to PEX substitutions

    See which PEX size matches the bore of an existing copper line before a repipe.

  • Hydronic and process loops

    Pick a pipe size for a circulator flow at a target velocity, then read the head loss for pump selection.

  • Irrigation and outbuildings

    Size a PVC run to a garden, barn or workshop and estimate the pressure left at the far end.

Tips and limitations

  • Where the static pressure at any fixture may exceed 550 kPa, NPC 2025 Sentence 2.6.3.3.(1) requires a pressure-reducing valve.
  • Provinces adopt the NPC with their own changes (Ontario in Part 7 of its Building Code, for example), so check the edition in force where you build.
  • Add an equivalent length for every elbow, tee and valve before you compare the loss with the pressure you have.
  • Each storey of rise costs about 30 kPa (9.8 kPa per metre), on top of friction.

Sources and further reading

  1. National Plumbing Code of Canada 2025, National Research Council Canada (NRC Publications Archive, free PDF). Division B, Subsection 2.6.3: 2.6.3.1.(1) peak demand, 2.6.3.3.(1) 550 kPa pressure-reducing valve, 2.6.3.4.(1) NPS ¾ minimum service, 2.6.3.4.(5) and Table 2.6.3.4, 2.6.3.5.(1) velocity.
  2. National Plumbing Code of Canada 2025 (catalogue record), Government of Canada Publications

Frequently asked questions

What is the minimum water service size in Canada?

NPC 2025 Sentence 2.6.3.4.(1) says water service pipes are sized for peak demand but must not be less than NPS ¾. Check the edition your province enforces.

What water velocity does the National Plumbing Code allow?

Sentence 2.6.3.5.(1) sets the maximum permitted velocities as those recommended by the pipe and fitting manufacturer. Table 2.6.3.4 for houses is laid out in columns for 3.0, 2.4 and 1.5 m/s.

When can I use the NPC sizing table for a house?

Under NPC 2025 Sentence 2.6.3.4.(5), Table 2.6.3.4 may be used for buildings with one or two dwelling units, or row houses with separate water service pipes, where the minimum pressure at the building entry is 200 kPa and the total length of the water system is no more than 90 m.

Is ¾ inch PEX enough for a house service?

Often not. Its bore is about 0.68 in, so at 0.6 L/s it would exceed 2.4 m/s. The calculator picks 1 in PEX for that flow.

How do I convert L/s to US gallons per minute?

Multiply by 15.85. A 0.6 L/s demand is about 9.5 US gpm. Imperial gallons are larger, so 0.6 L/s is about 7.9 imperial gpm.

Is there an in-depth guide to the Water Pipe Size Calculator?

Yes. “Water Pipe Sizing by Velocity and Hazen-Williams Friction Loss” covers the background, how it works, common pitfalls and worked examples. Read the full guide.