Canada version. Keeps cfm and inches for forced-air work, as Canadian HVAC trades do, with NBC 2025 Subsection 9.32.3 ventilation fan rates in cfm and L/s. US version
Duct Size Calculator for Furnaces and HRVs (Canada)
Size round and rectangular ducts for a furnace, heat pump or HRV in cfm and inches, or L/s and mm, with friction per 100 ft and NBC fan capacities.
The interactive tool loads here when JavaScript runs.
About this toolWhat is the Duct Size Calculator?
Most Canadian houses heat with forced air, so duct sizing usually starts from the furnace or heat pump blower: the heat loss is calculated to CSA F280, equipment is picked, and its airflow in cfm is split between trunks and runs. Trade practice here stays in cfm, inches and inches of water column, so this version opens in US units with a trunk-sized airflow.
Ventilation is a separate job under the National Building Code. NBC 2025 Table 9.32.3.3 sizes the principal ventilation fan by bedrooms, 22 to 32 L/s (47 to 68 cfm) for three, and Article 9.32.3.7 asks for supplemental fans of at least 25 L/s (53 cfm) in bathrooms the principal fan does not serve and 50 L/s (106 cfm) in the kitchen. Those small flows need their own duct checks, especially through flex.
- Velocity and equal-friction sizing in US or metric units
- Darcy-Weisbach with Colebrook friction and five roughness categories
- Next standard round size in inch or EN 1506 metric series
- Rectangular equivalents from the Huebscher formula with aspect ratio
- Typical design velocity table and velocity pressure for fitting losses
Updated
How to use the Duct Size Calculator
- Keep US units for forced air, or switch to SI and L/s for HRV and fan work.
- Enter the blower or branch airflow in cfm.
- Use equal friction (often 0.06 to 0.10 in.wg per 100 ft for houses) for trunks, or velocity for a single fan.
- Pick galvanized for sheet-metal trunks and flexible for flex runs, then add the fittings before you compare with the blower's external static pressure.
Worked examples
Supply trunk for a 1,200 cfm blower
Input
1,200 cfm, 0.08 in.wg per 100 ft, galvanized steel
Output
15.30 in exact, 16 in round at 859 fpm; rectangular 21 x 10 or 17 x 12 in at about the same friction
A 10 in deep rectangular trunk saves headroom under a basement ceiling. At 0.10 in.wg per 100 ft the trunk drops to 15 in round, at nearly 1,000 fpm.
Bathroom fan at the 25 L/s (53 cfm) minimum
Input
53 cfm, 4 in duct, smooth then flexible
Output
Smooth: 607 fpm, 0.181 in.wg per 100 ft. Flex: 0.402 in.wg per 100 ft; 6 in flex drops to 0.046
Bathroom fans are rated at a stated static pressure. A long 4 in flex run to a roof cap can halve the delivered airflow, so use 6 in or rigid duct where you can.
Principal ventilation fan, three bedrooms
Input
67.8 cfm (32 L/s, the top of the 22 to 32 L/s range), 0.1 in.wg per 100 ft, galvanized
Output
5.00 in exact, 5 in round at 497 fpm and 0.100 in.wg per 100 ft
NBC 2025 sets the capacity by bedroom count (Table 9.32.3.3). HRV ducts are often sized larger than this to keep the unit quiet and easy to balance.
Background and insight
The velocity method uses continuity alone: area equals airflow divided by velocity, so D = √(4Q/πV). It is simple and controls noise, but it ignores how much pressure the run will consume. The equal-friction method fixes the pressure loss per unit length instead, so every branch of a system loses pressure at a similar rate, which makes balancing easier. Residential designers commonly use 0.06 to 0.10 in.wg per 100 ft; ACCA Manual D derives the actual rate from the fan's available static pressure and the longest run.
Friction in a round duct follows the Darcy-Weisbach equation, Δp/L = (f/D)·ρV²/2. The friction factor f comes from the Colebrook equation, which depends on the Reynolds number and the relative roughness ε/D. ASHRAE classes galvanized steel ducts as medium smooth with ε = 0.09 mm (0.0003 ft), the basis of its friction chart, and lists smoother and rougher categories for other materials. Flexible duct, even fully stretched, is far rougher, and sagging or compressed flex can double the loss again.
A rectangular duct does not have the same friction as a round duct of equal area, because its corners add wetted perimeter. Huebscher (1948) gave the equivalent diameter that carries the same airflow at the same friction: De = 1.30 (ab)^0.625 / (a + b)^0.25. A 12 x 12 in duct is equivalent to 13.1 in round, not the 13.5 in its area would suggest. Aspect ratios above about 4:1 waste metal and pressure, and are best avoided.
Common use cases
Residential duct layouts
Size trunks and branch runs for a furnace or heat pump from room airflows and a target friction rate.
Ventilation and extract systems
Pick duct sizes for an MVHR unit, a bathroom fan run or a kitchen extract in metric or US units.
Swapping round for rectangular
Find a rectangular section that fits a ceiling void or joist bay without losing airflow or adding friction.
Checking an existing duct
Enter the airflow and see what friction and velocity a given round size produces, to explain noise or low airflow.
Tips and limitations
- Heat loss and equipment size come from CSA F280; the duct sizes follow from the chosen equipment's airflow, not the other way round.
- NBC 9.32.3.2 points to good practice such as the HRAI Digest and the HRAI Residential Mechanical Ventilation Manual for the parts of a ventilation system the code does not spell out, including duct design.
- Insulate and seal ducts that run through unheated attics or garages to stop condensation and heat loss in winter.
- Kitchen exhaust in a tight house may need make-up air; check Article 9.32.3.8 where there are fuel-fired space- or water-heating appliances that are not direct-vented or mechanically vented.
Sources and further reading
- National Building Code of Canada 2025, National Research Council Canada. NRC Publications Archive (free PDF). Division B, Subsection 9.32.3: Table 9.32.3.3 principal fan capacity by bedrooms, 9.32.3.2 good practice (HRAI), 9.32.3.7 supplemental exhaust 25 L/s and 50 L/s, 9.32.3.8 depressurization.
- National Building Code of Canada 2025 (catalogue record), Government of Canada Publications
Frequently asked questions
What size duct for a 1,200 cfm furnace?
At 0.08 in.wg per 100 ft in galvanized steel, a 16 in round trunk or a 21 x 10 in rectangular one. The real friction rate comes from the blower's available static pressure after filters, coil and fittings.
How many cfm does a bathroom fan need under the NBC?
NBC 2025 Sentence 9.32.3.7.(4) asks for a supplemental exhaust fan of at least 25 L/s (53 cfm) in each bathroom or water-closet room the principal fan does not draw from, and Sentence (1) at least 50 L/s (106 cfm) in the kitchen. Provinces adopt the code with changes, so check the edition in force.
What duct size does an HRV need?
Size each HRV duct for the flow it carries. At the top of the three-bedroom range, 32 L/s (67.8 cfm), a galvanized round duct at 0.1 in.wg per 100 ft comes out at 5 in; a size up lowers the friction and the noise. The required fan rates by bedroom count are on the [air changes calculator](/en-ca/air-changes-calculator).
What is 25 L/s in cfm?
About 53 cfm (1 L/s is 2.119 cfm, 1 cfm is 0.472 L/s). Switch the calculator to SI and L/s to work in the units the NBC tables use.
Should I use flex duct for a bathroom fan?
Keep it short and pulled tight, or use rigid duct. At 53 cfm a 4 in flex run has more than twice the friction of smooth duct of the same size.
Is there an in-depth guide to the Duct Size Calculator?
Yes. “Duct Sizing: The Velocity and Equal-Friction Methods Explained” covers the background, how it works, common pitfalls and worked examples. Read the full guide.