U-Value and Heat Loss Calculator (UK)
Work out the U-value of a wall, loft or floor in W/m²K, check it against the Part L limiting values and see the heat loss in watts at a CIBSE design temperature.
The interactive tool loads here when JavaScript runs.
About this toolWhat is the Heat Loss and U-Value Calculator?
In England a new wall, roof or floor is judged by its U-value in W/m²K. Approved Document L Volume 1 sets the limiting values: for a new dwelling a wall may not exceed 0.26 and a roof 0.16 (Table 4.1), and for an extension or a replacement element in an existing home the wall limit tightens to 0.18 and the roof to 0.15 (Table 4.2). Building control will ask for a U-value calculation for each element, usually from the insulation maker or an assessor working to BR 443 and BS EN ISO 6946.
Enter the build-up from the inside face outwards, with each thickness in millimetres and each conductivity in W/mK from the product datasheet, then type the limit you are designing to. The default is a timber frame wall with 140 mm of mineral wool and a brick outer leaf: it comes to 0.23 W/m²K, inside the new-build limit but well short of the 0.18 an extension needs.
The heat loss in watts is the figure a heat pump survey builds on. MCS installers use a room-by-room method to BS EN 12831-1, with an outside design temperature taken from the nearest of 14 CIBSE Guide A weather stations (London Heathrow is -3.0 °C at 99.6%) and inside temperatures from the CIBSE domestic heating guide, typically 21 °C for living rooms and 22 °C for bathrooms.
- Up to ten layers by thickness and conductivity or by known R-value
- ISO 6946 and ASHRAE surface resistances for walls, roofs and floors
- R-value and U-value in both SI and US units at once
- Heat loss in watts and BTU/h, plus seasonal kWh and therms from degree-days
- Layer share table and steady-state interface temperatures
Updated
How to use the Heat Loss and U-Value Calculator
- Keep the units on metric and list the layers from the room side: plasterboard, insulation, sheathing or block, cavity, outer leaf.
- Replace the typical conductivity with the declared lambda value on the product datasheet, for example 0.022 W/mK for many PIR boards.
- Pick the ISO 6946 surface resistances for a wall, a roof (heat flow up) or a floor (heat flow down).
- Enter the limiting U-value you are designing to: 0.26 or 0.18 for walls, 0.16 or 0.15 for roofs, 0.18 for floors.
- Set the outside temperature for your nearest CIBSE station and the heating degree days for your postcode area for a seasonal estimate.
Worked examples
Rear extension wall against the 0.18 limit
Input
12.5 mm plasterboard, 100 mm aircrete block (k 0.16), PIR in the cavity (k 0.022), 0.18 cavity, 102.5 mm brick; 20 m², 21 °C in, -5.1 °C out (Birmingham)
Output
100 mm PIR: U 0.175 W/m²K, meets 0.18, 91.5 W; 90 mm PIR: U 0.191, fails, 99.4 W
The extra 10 mm of board is what takes the wall under the Table 4.2 limit. Wall ties and the frame of any window reveal add bridging that this clear-field figure leaves out, so the maker's calculation for the full build-up should still have some margin.
Solid brick wall upgraded from the inside
Input
215 mm solid brick (k 0.77), then the same wall lined with 70 mm PIR (k 0.022) and 12.5 mm plasterboard; 12 m², 21 °C to -3 °C
Output
Bare brick U 2.23 W/m²K and 641 W; insulated U 0.272 W/m²K and 78 W
Approved Document L Table 4.3 asks a renovated solid wall to reach 0.30 where that is feasible. 50 mm of PIR gives 0.361 and falls short; 70 mm reaches 0.272. Internal insulation on solid walls needs a moisture risk check, so ask for a condensation risk analysis to BS EN ISO 13788.
Loft insulation and a year of heating
Input
12.5 mm plasterboard ceiling with 270 mm glass fibre (k 0.04), roof films; 45 m², 21 °C to -3 °C, 2,033 degree days (EC postcode area, base 15.5 °C)
Output
U 0.144 W/m²K, 155.6 W at design, about 316 kWh a year before heating efficiency; with only 100 mm: U 0.372, 401.5 W and 816 kWh
Topping up an old 100 mm loft to 270 mm cuts the heat lost through that ceiling by about 60%. The 0.16 roof limit for new homes is met by the 270 mm build-up in the clear field; joists between the quilt add bridging.
Background and insight
The method is the one in ISO 6946 and the ASHRAE Handbook of Fundamentals: thermal resistances of layers that the heat crosses one after another simply add, R = d / k for each homogeneous layer, and U is the reciprocal of the total. Surface resistances account for the thin film of still air on each face. ISO 6946 uses 0.13 m²·K/W inside for walls, 0.10 for heat flowing up through a roof or ceiling, 0.17 for heat flowing down through a floor, and 0.04 outside. ASHRAE tabulates the same idea in US units: R-0.68 for still air on a vertical surface and R-0.17 for a 15 mph winter wind.
US and SI R-values describe the same property in different units, which is why a product sold as R-13 in the United States is RSI 2.29 elsewhere. One m²·K/W equals 5.678 ft²·°F·h/BTU. Conductivities in the material list are typical design values from ISO 10456, CIBSE Guide A and manufacturer literature; insulation products vary with density and age, so the declared lambda value on the datasheet should replace the default whenever you have it.
A clear-field calculation like this ignores thermal bridges. In a timber stud wall the studs occupy roughly 15 to 25% of the area and conduct three times better than mineral wool, so the whole-wall U-value is noticeably worse than the clear-field one. Steel studs are far worse again. Full heat-load methods (ACCA Manual J, EN 12831) add bridging, ventilation and infiltration on top of the fabric losses calculated here.
Common use cases
Comparing insulation upgrades
See how much an extra 50 mm of PIR board or a thicker batt changes the U-value and the seasonal kWh before pricing the work.
Building regulations checks
Check that a proposed wall or roof meets a target U-value such as 0.18 or 0.26 W/m²·K, then confirm with a full ISO 6946 calculation including bridging.
Sizing a room heater
Add up the fabric losses of each wall, ceiling and floor to get a first estimate of the heat a room needs at the design outdoor temperature.
Condensation screening
Use the interface temperatures to see where a wall drops below the indoor dew point and where a vapour control layer belongs.
Tips and limitations
- Product lambda values on UK datasheets are declared to BS EN 13162 to 13171; use the declared value, not a marketing "equivalent" figure.
- For a heat pump, MCS asks for a room-by-room heat loss; this element figure is one row of that sheet, not the whole house.
- The degree days in the MCS calculator use a 15.5 °C base, so enter them as K·day.
Sources and further reading
- Approved Document L: Conservation of fuel and power, Volume 1 dwellings (2021 edition incorporating 2023 amendments), GOV.UK, Department for Levelling Up, Housing and Communities. Tables 4.1, 4.2 and 4.3: limiting U-values for new dwellings, new elements in existing dwellings and renovated elements; paragraph 4.1 on BR 443. The 2026 edition, taking effect on 24 March 2027, keeps these values in Tables 3.1 to 3.3.
- MCS Heat Load Calculator: design conditions, MCS Certified. External design temperatures from CIBSE Guide A Table 2.5, altitude correction, degree days at 15.5 °C base and internal design temperatures.
- Building regulations approval, GOV.UK
Frequently asked questions
What U-value does a wall need to meet Building Regulations in England?
For a new dwelling the limiting wall U-value is 0.26 W/m²K (Approved Document L Volume 1, Table 4.1), though the energy target usually pushes designs nearer 0.18. A new wall in an extension or existing home must reach 0.18 (Table 4.2), and a renovated wall should reach 0.30 with internal or external insulation, or 0.55 for cavity fill (Table 4.3, column b).
What U-value does a loft or roof need?
A roof on a new dwelling may not exceed 0.16 W/m²K and a new roof element in an existing home 0.15. When a loft is renovated, an existing roof worse than 0.35 should be improved to 0.16 where that is technically feasible and pays back within 15 years.
Which outside design temperature do heat pump installers use?
The MCS heat load calculator takes the nearest of 14 CIBSE Guide A stations to your postcode and lowers the temperature by 0.6 °C for every 100 m your home sits above that station. Examples at 99.6%: London Heathrow -3.0 °C, Birmingham -5.1 °C, Manchester -4.5 °C, Glasgow -5.6 °C, Plymouth -1.5 °C.
What inside temperatures go into a UK heat loss calculation?
The MCS calculator uses the CIBSE Domestic Heating Design Guide: 21 °C for living and dining rooms, 22 °C for bathrooms and shower rooms, and for older homes 18 °C for bedrooms, halls and kitchens. Newer, well-insulated homes are designed at 21 °C throughout except bathrooms at 22 °C.
Is the U-value from this calculator the one building control will accept?
It is a clear-field figure: layers in series with no studs, joists, wall ties or fixings. Approved Document L asks for U-values assessed to BR 443, which applies BS EN ISO 6946 corrections for bridging and fixings. Use this tool to compare options and size insulation, then get the formal calculation from the insulation maker or an assessor.
How do I work out the heat loss through a wall in watts?
Multiply the U-value by the net area and by the difference between inside and outside design temperatures. A 20 m² wall at 0.23 W/m²K between 21 °C and -3 °C loses about 112 W. Windows and doors are calculated separately with their own U-values.
Is there an in-depth guide to the Heat Loss and U-Value Calculator?
Yes. “U-Value, R-Value and Heat Loss: Calculating a Wall Layer by Layer” covers the background, how it works, common pitfalls and worked examples. Read the full guide.