Three-Phase Power Calculator (Australia, 230/400 V)
Convert kW, kVA and motor kW ratings to amps on a 230/400 V 50 Hz supply, and check when a motor needs three-phase under the NSW service rules.
The interactive tool loads here when JavaScript runs.
About this toolWhat is the Three-Phase Power Calculator?
Australian low-voltage supply is 230 V from line to neutral and 400 V between lines at 50 Hz, delivered as a three-phase, four-wire system. This version starts there and takes motor ratings in kW, as they appear on the plate. A 22 kW motor at 92.6% efficiency and power factor 0.86 draws 39.9 A per line on 400 V.
Distributors set rules on top of AS/NZS 3000 for what can go on a single-phase supply. In NSW, the Service and Installation Rules require three phases and neutral for a motor over 2 kW and for a maximum demand above 100 A per phase, and they cap motor starting currents. Use the running current from this calculator as the first step, then check the starting current against your distributor's limit.
The same arithmetic helps with ducted air conditioning, pool and bore pumps, workshop compressors and three-phase EV chargers, where the question is often whether a single-phase supply will do.
- Single-phase and three-phase, line-to-line or line-to-neutral voltage
- Solve from amps, kW, kVA or horsepower
- Power factor, efficiency, kVAR and phase angle
- Comparison table of current at other power factors
- Formula panel with your numbers, copy and share
Updated
How to use the Three-Phase Power Calculator
- Pick single-phase, three-phase with line-to-line voltage, or three-phase with line-to-neutral voltage.
- Enter the voltage. The preset buttons cover common systems such as 208, 400, 480 and 600 V line to line or 120, 230 and 277 V line to neutral.
- Choose what you know: current, kW, kVA or motor horsepower, and type the value.
- Enter the power factor (1 for resistive heaters, 0.8 to 0.9 for loaded induction motors) and, for motors, the nameplate efficiency.
- Read current, kW, kVA, kVAR and shaft output, and check the formula panel to see the numbers substituted.
Worked examples
22 kW motor on a 400 V switchboard
Input
3-phase 400 V, motor rated output 22 kW, PF 0.86, efficiency 92.6%
Output
39.87 A per line; 23.76 kW drawn, 27.63 kVA
Under the NSW rules a non-domestic three-phase motor may start at up to 3.3 × 22 + 53 = 125.6 A. A direct-on-line start of a motor this size is several times its running current, so a soft starter or variable speed drive is usually needed to stay inside that limit.
2.2 kW pump: single-phase or three-phase
Input
Single-phase 230 V, 2.2 kW output, PF 0.9, efficiency 80%; then 3-phase 400 V, PF 0.8, efficiency 85%
Output
13.29 A single-phase; 4.67 A per line three-phase
At 2.2 kW the motor is over the 2 kW threshold in Table 1-1 of the NSW rules, so the distributor can require it on three phases. Ask before buying a single-phase unit.
Is 100 A per phase the same as 69 kW?
Input
3-phase 400 V, 100 A, PF 1
Output
69.28 kVA, 69.28 kW
That is the point where the NSW rules move an installation onto three phases regardless of what it supplies. At PF 0.9 the same 100 A carries 62.4 kW.
15 kW ducted air conditioning
Input
3-phase 400 V, real power 15 kW, PF 0.9
Output
24.06 A per line, 16.67 kVA
Use the electrical input from the unit's data plate here. The cooling capacity in the brochure is a different number and is not what the supply carries.
Background and insight
For a balanced three-phase load the apparent power is S = √3 × V(LL) × I, where V(LL) is the line-to-line voltage and I the current in each line. The √3 comes from the 120° spacing of the phases: the voltage between two lines is √3 times the voltage from a line to neutral, and three phases each carry V(LN) × I, so S = 3 × V(LN) × I = √3 × V(LL) × I. Single-phase is simply S = V × I.
Real power, the part that does work and that a kWh meter bills, is P = S × PF. Reactive power, which circulates between the supply and the magnetic fields of motors and transformers, is Q = S × sin φ, where φ = arccos PF. Cables, breakers and transformers must carry the full current, so they are rated in amps or kVA, not kW. A 100 A load at 480 V and PF 0.85 is 83.1 kVA but only 70.7 kW.
Motor nameplates give output power in horsepower or kW at the shaft. The electrical input is the output divided by efficiency, so a 10 hp motor (7.457 kW) at 90% efficiency draws 8.29 kW from the supply. One horsepower is 745.7 W (NIST SP 811). For wiring and protection the NEC uses its own full-load current tables (430.248 for single-phase, 430.250 for three-phase) rather than nameplate amps, because they are deliberately conservative.
Common use cases
Feeder and breaker checks
Convert a kW or kVA schedule into amps to choose cables, breakers and busbars.
Motor circuits
Estimate the running current of a pump, fan or compressor from its horsepower, efficiency and power factor.
Generator and UPS loading
Turn measured amps into kVA and kW to compare with a generator or UPS rating.
Reading meter data
Make sense of a power analyser reading by relating amps, kW, kVA and kVAR.
Tips and limitations
- If the 10-minute average voltage at your main switchboard sits above 253 V with nothing running, the NSW rules say to contact the distributor. High voltage raises currents in resistive loads and stresses inverters.
- Some outlying areas have a 230/460 V two-phase, three-wire supply instead of three-phase. Ask the distributor what you have before buying three-phase equipment.
- For motors, use "Motor rated output (kW)". Entering the plate kW as real power leaves out the motor's losses.
- Cable sizes come from AS/NZS 3008.1.1 and the installation must meet AS/NZS 3000. This calculator gives the current those steps start from.
Sources and further reading
- Service and Installation Rules of NSW (April 2026), NSW Department of Climate Change, Energy, the Environment and Water. Clause 1.11.1 (230/400 V, 50 Hz), Table 1-1 (number of phases) and Table 1-3 (motor starting currents).
- AS/NZS 3000 Electrical installations (Wiring Rules), Standards Australia
Frequently asked questions
Is Australian three-phase 400 V or 415 V?
The nominal supply is 230/400 V at 50 Hz under AS IEC 60038, which the NSW Service and Installation Rules cite. Older equipment and drawings may still say 240/415 V, the former nominal. Enter the voltage on your drawing or rating plate.
When do I need three-phase power for a motor?
In NSW, Table 1-1 of the Service and Installation Rules requires three phases and neutral for a motor exceeding 2 kW, and for any installation whose maximum demand exceeds 100 A per phase. Other states and distributors set their own thresholds, so check your local service rules.
How much starting current can a motor draw?
The NSW rules give a guide in Table 1-3: 45 A for a single-phase 230 V motor, 53 A for a domestic three-phase 400 V motor, and 3.3 × kW + 53 A for a non-domestic three-phase motor, where kW is the output of the largest motor started at once. The starting current must not drop the voltage at the connection point by more than 5% for more than 20 milliseconds.
How many amps is a 7.5 kW three-phase motor?
Enter its plate efficiency and power factor. With 90% and 0.84 it draws about 14.3 A per line at 400 V. Without the plate figures, assume efficiency and power factor are lower than ideal rather than leaving them at 100% and 1.
Can I run a three-phase motor on a single-phase supply?
Only through a drive or converter rated for it, and the single-phase line then carries about three times the per-line current of a 400 V three-phase supply for the same power. The distributor's phase rules still apply to the installation.
Does this size my cable?
No. It gives the load current. Cable selection follows AS/NZS 3008.1.1 for current-carrying capacity and voltage drop, and the work must be done by a licensed electrician.
Is there an in-depth guide to the Three-Phase Power Calculator?
Yes. “The Three-Phase Power Formula: Where √3 Comes From” covers the background, how it works, common pitfalls and worked examples. Read the full guide.