South Africa version. Set for 400 V, 50 Hz and a 0.96 target, the point where reactive energy above 30% of kWh starts to be billed on Eskom's Megaflex and Miniflex tariffs in June to August. US version
Power Factor Correction Calculator (South Africa, 400 V 50 Hz)
Size a capacitor bank in kVAr for a 400 V, 50 Hz supply and see why Eskom's reactive energy charge starts below a 0.96 power factor in the winter months.
The interactive tool loads here when JavaScript runs.
About this toolWhat is the Power Factor Correction Calculator?
On Eskom's time-of-use business tariffs, poor power factor costs money in a very specific way. The 2026/27 tariff booklet charges for reactive energy (kVArh) above 30% of the active energy (kWh), which it describes as a power factor of 0.96 or less, and only in the high-demand season from 1 June to 31 August. This version therefore opens on a 400 V, 50 Hz delta bank aimed at 0.96 rather than the 0.95 often quoted elsewhere.
Enter the average kW of the site and the power factor from your bill or a logger. The calculator gives the kVAr of capacitors needed, the capacitance per capacitor at 50 Hz and the drop in current and kVA. A 250 kW load at 0.85 needs 82.0 kVAr to reach 0.96, and the line current falls from 424.5 A to 375.9 A.
The kVA saving matters as much as the reactive charge. Megaflex and Miniflex bill network capacity in rand per kVA on the higher of your notified maximum demand (NMD) and the measured maximum demand, so a lower kVA can keep a growing plant inside its NMD without an upgrade application.
- kVAR from kW and two power factors, with the catalogue multiplier
- Capacitance per capacitor for single-phase, delta and star at 50 or 60 Hz
- Current, kVA and cable loss before and after
- Scaled power triangle
- Warnings for over-correction targets
Updated
How to use the Power Factor Correction Calculator
- Enter the real power in kW. Use average demand from a bill or logger rather than a nameplate total.
- Enter the existing power factor and the target. 0.95 is a common target; going past 0.98 rarely pays and risks over-correction at light load.
- Enter the voltage (line to line for three-phase) and frequency.
- Choose single-phase, three-phase delta or three-phase star for the capacitor connection.
- Read the kVAR, the capacitance per capacitor, the current before and after, and the released kVA.
Worked examples
Workshop on Miniflex at 0.85, target 0.96
Input
250 kW, PF 0.85 to 0.96, 400 V, 50 Hz, delta
Output
82.02 kVAr; 543.9 µF per capacitor; 424.5 A to 375.9 A; 294.1 kVA to 260.4 kVA
About 34 kVA of capacity comes back. Most suppliers would offer an automatic bank of about 80 to 90 kVAr in steps, so the correction follows the load instead of over-correcting at night.
What the winter reactive charge adds up to
Input
Miniflex, 120 000 kWh in a June billing period at an average PF of 0.85
Output
74 369 kVArh recorded; 36 000 kVArh allowed (30%); 38 369 kVArh excess, about R5 763 before VAT at 15.02 c/kVArh
At PF 0.85 the reactive energy is 0.62 kVArh for every kWh. Miniflex works out the excess on the billing-period totals, and the 2026/27 rate is 15.02 c/kVArh (17.27 c with VAT) from June to August and zero for the rest of the year. Three winter months at that level cost roughly R17 000 before VAT, which is the figure to set against the price of a bank.
Only reaching the Distribution Code minimum
Input
250 kW, PF 0.85 to 0.90, 400 V, 50 Hz, delta
Output
33.86 kVAr; 224.5 µF; 400.9 A; 277.8 kVA
The South African Distribution Network Code asks customers above 100 kVA to stay at or above 0.9 lagging. That avoids the compliance problem but not the tariff: 0.90 is still well below 0.96, so reactive energy above the 30% allowance would still be billed in winter.
Large Megaflex site at 0.88
Input
1 200 kW, PF 0.88 to 0.96, 400 V, 50 Hz, delta
Output
297.7 kVAr; 1 968 A to 1 804 A; 1 363.6 kVA to 1 250 kVA
Measured on the 400 V side of the site's own transformer, since a site this size is normally supplied at medium voltage. On Megaflex the excess is measured in every 30-minute period during peak and standard hours, not on monthly totals, so a bank that drops out during the morning peak still leaves a charge. Size the steps for the peak-hour load.
Background and insight
Induction motors, transformers and fluorescent ballasts draw magnetising current that lags the voltage. That reactive current does no work, but it flows through every cable and transformer between the source and the load. Power factor, PF = kW ÷ kVA = cos φ, measures how much of the current is useful. Many utilities add a charge when the monthly PF falls below a threshold, commonly 0.9 or 0.95, or bill on kVA demand.
A capacitor draws leading reactive current that cancels part of the lagging current. With real power P unchanged, the reactive power before correction is P × tan φ1 and after is P × tan φ2, so the capacitor must supply Qc = P × (tan φ1 − tan φ2). Raising 100 kW from PF 0.70 to 0.95 needs 100 × (1.0202 − 0.3287) = 69.15 kVAR. Current falls in proportion to PF1 ÷ PF2, here by 26%, and cable losses (proportional to current squared) fall by about 46%.
Capacitance follows from Q = V² × 2πf × C for each capacitor. A single-phase capacitor across V needs C = Q ÷ (2πfV²). In a three-phase delta bank each of three capacitors sees the full line voltage and supplies Q ÷ 3, so C = Q ÷ (3 × 2πf × V²). In a star bank each sees V ÷ √3, which makes each capacitor three times larger: C = Q ÷ (2πf × V²). Delta banks are therefore usual at low voltage. Standard references include IEEE Std 18 for shunt power capacitors and IEC 60831 for low-voltage self-healing units.
Common use cases
Avoiding utility PF penalties
Size a capacitor bank to keep the monthly power factor above the tariff threshold.
Freeing transformer capacity
See how many kVA correction releases before buying a larger transformer.
Motor capacitor selection
Find the µF for an individual motor capacitor at 50 or 60 Hz.
Teaching the power triangle
Show how kW, kVA and kVAR relate before and after correction.
Tips and limitations
- Read your bill for the kVArh and kWh in peak and standard periods. On Megaflex the 30% allowance is checked per half-hour; on Miniflex and Ruraflex it uses the billing-period totals.
- Variable speed drives, UPS systems and LED drivers add harmonics. Where they are a large share of the load, ask for a detuned bank with reactors to avoid resonance with the supply transformer.
- The Distribution Network Code also says power factor must not go leading unless agreed with the distributor, so automatic step switching matters on sites that idle at night or over weekends.
- The same code asks you to inform your distributor before installing shunt capacitors, so tell Eskom or your municipality before the bank goes in.
Sources and further reading
- Tariffs and Charges Booklet 2026/2027, Eskom Distribution. Reactive energy charge above 30% of kWh (0.96 power factor or less), high-demand season June to August; Megaflex 34.49 and Miniflex 15.02 c/kVArh before VAT.
- South African Distribution Network Code, version 6.2, NERSA / Eskom Distribution. Clause 6.3: customers above 100 kVA keep power factor at or above 0.9 lagging and inform the distributor before installing shunt capacitors.
- SANS 1019:2021 Standard voltages, currents and insulation levels for electricity supply, South African Bureau of Standards. Scope: standard voltages and currents for a.c. systems with a nominal frequency of 50 Hz, based on IEC 60038.
Frequently asked questions
At what power factor does Eskom start charging for reactive energy?
On tariffs such as Megaflex, Miniflex and Ruraflex, the 2026/27 booklet charges for reactive energy supplied in excess of 30% of the kWh, which it equates to a power factor of 0.96 or less. Mathematically, kVArh equal to 30% of kWh is a power factor of about 0.958. The charge applies only in the high-demand season, 1 June to 31 August.
How much is the reactive energy charge?
For non-local-authority customers from 1 April 2026, the booklet lists 34.49 c/kVArh (39.66 c with VAT) on Megaflex and 15.02 c/kVArh (17.27 c with VAT) on Miniflex in the high-demand season, and 0.00 c in the low-demand season. Municipal tariffs are set by each municipality, so check your own tariff schedule if the municipality supplies you.
Do homes in South Africa pay for poor power factor?
No. The residential tariffs (Homelight, Homepower and Homeflex) have no reactive energy charge, so correcting power factor at home saves nothing on the bill. It is a business tariff issue.
Is 0.9 enough to comply?
For customers with a demand above 100 kVA, the Distribution Network Code (version 6.2, clause 6.3) sets a minimum of 0.9 lagging and says the power factor must not go leading unless agreed with the distributor. Compliance and tariff are different questions: 0.9 meets the code but still attracts the winter reactive charge.
Should I use 50 Hz or 60 Hz?
Always 50 Hz in South Africa. SANS 1019 covers standard voltages for systems with a nominal frequency of 50 Hz. Using 60 Hz in the calculator would understate the capacitance needed by a sixth.
Will correction lower my demand charge?
It lowers the kVA you draw for the same kW. Megaflex and Miniflex network charges are in R/kVA on the annual utilised capacity (the higher of NMD and measured maximum demand), so a lower kVA helps when you renegotiate the NMD or when you are close to exceeding it.
Is there an in-depth guide to the Power Factor Correction Calculator?
Yes. “Power Factor Correction: Sizing Capacitors in kVAR and µF” covers the background, how it works, common pitfalls and worked examples. Read the full guide.