Air Changes per Hour and NCC Exhaust Fan Rates
Turn an exhaust fan's m³/h or L/s into air changes for your bathroom, laundry or kitchen, and check it against the NCC 25 L/s and 40 L/s minimums.
By Redbison Dev · · 9 min read

Australia edition. Written for Australian homes under the NCC 2025 Housing Provisions, with the 25 L/s and 40 L/s exhaust minimums, discharge to outdoor air, run-on timers, make-up air, the 5% natural ventilation rule and fans rated in m³/h. US edition
Australian homes do not have a whole-house air change target in the National Construction Code. What the NCC 2025 Housing Provisions do set are minimum exhaust rates: 25 L/s for a bathroom or toilet and 40 L/s for a kitchen or laundry, discharged to outdoor air, never into the roof space. Air changes per hour are still the clearest way to see whether a fan will clear the steam from your particular room, and this guide works them out with the Australian version of the Air Changes per Hour Calculator.
From the fan box to air changes
Fans sold in Australia are usually rated in cubic metres per hour, while the NCC speaks in litres per second:
L/s = m³/h / 3.6
ACH = airflow (m³/h) / room volume (m³)
So the 25 L/s bathroom minimum is 90 m³/h, and the 40 L/s kitchen and laundry minimum is 144 m³/h. A ceiling fan sold as 250 m³/h moves about 69 L/s on paper. A small 90 m³/h unit sits exactly on the bathroom minimum, with nothing in hand for the duct.
That margin matters, because box ratings are measured with free air on both sides. Flexible duct, bends, a long run to the eaves and a roof cowl all reduce the real flow.
What NCC 10.8.2 asks for
Part 10.8 of the Housing Provisions, which deals with condensation, sets out exhaust systems in 10.8.2:
| Requirement | NCC 2025 Housing Provisions 10.8.2 |
|---|---|
| Bathroom or sanitary compartment | at least 25 L/s |
| Kitchen or laundry | at least 40 L/s |
| Where the air goes | directly, or through a shaft or duct, to outdoor air (kitchens, range hoods, bathrooms, toilets and laundries) |
| Venting clothes dryer | also discharges to outdoor air |
| Bathroom or toilet not naturally ventilated, fan not continuous | interlocked with the light, with a run-on timer of 10 minutes after the light goes off |
| Make-up air for exhausted rooms not naturally ventilated | openings to an adjacent room with 14,000 mm² free area, or to AS 1668.2 |
| Room with a venting clothes dryer | make-up air to AS 1668.2 |
A 14,000 mm² opening is, for example, a 20 mm gap under a 700 mm door. Without make-up air, a fan in a closed bathroom just strains against the door and moves far less than its rating.
The energy efficiency part adds one more detail. Housing Provisions 13.4.5 asks exhaust fans serving conditioned spaces, or habitable rooms in climate zones 4 to 8, to have a sealing device such as a self-closing damper, so the fan is not a hole in the ceiling when it is off.
Worked examples
Each of these is a fan at the NCC minimum in a typical room, entered into the calculator in metres with the flow in m³/h:
| Room | Size | Fan | Air changes per hour | One change every | Time to clear 99% |
|---|---|---|---|---|---|
| Ensuite | 1.8 x 1.5 x 2.4 m (6.48 m³) | 25 L/s | 13.9 | 4.3 minutes | about 20 minutes |
| Family bathroom | 2.4 x 2.0 x 2.4 m (11.52 m³) | 25 L/s | 7.81 | 7.7 minutes | about 35 minutes |
| Laundry | 2.4 x 1.8 x 2.4 m (10.37 m³) | 40 L/s | 13.9 | 4.3 minutes | about 20 minutes |
| Open-plan kitchen and living | 7.0 x 5.0 x 2.7 m (94.5 m³) | 40 L/s range hood | 1.52 | 39 minutes | about 3 hours |
The same 25 L/s fan does twice as much work in the ensuite as in the family bathroom, simply because the room is smaller. In a large family bathroom, especially one with a high ceiling, choosing a fan well above the minimum is the difference between a mirror that clears before you dry off and one that does not.
The open-plan kitchen is the starkest case. A 40 L/s range hood is compliant, but as a share of the whole room it changes the air only one and a half times an hour. A hood works by catching steam and fumes at the cooktop before they spread, so run it on high while cooking and for a while after.
Where the clearing times come from
If incoming air is clean and mixes fully with the room, a pollutant falls exponentially:
C / C0 = e^(−ACH x t)
with t in hours. One air change leaves 37% behind, and 99% takes ln(100) = 4.6 air changes, so at 7.81 ACH that is 4.6 / 7.81 hours, about 35 minutes. Real rooms mix imperfectly, especially when the fan sits right above the door that supplies the make-up air, so treat these times as best cases. They also explain the 10-minute run-on: a fan that stops when the light goes off leaves most of the steam behind.
Natural ventilation: the 5% rule
Fans are one route. NCC Housing Provisions 10.6.2 lets a habitable room, bathroom or laundry be naturally ventilated instead, through openings with a ventilating area of at least 5% of the room's floor area, opening to the outside, an open verandah or carport, or a suitable adjoining room (a sanitary compartment cannot borrow ventilation through another room). For the 2.4 by 2.0 m family bathroom (4.8 m²), that is 0.24 m² of openable window.
Windows and fans are not interchangeable in one respect. An exhaust fan is still required at the rates above wherever one is installed, and the run-on timer and make-up air rules apply only to bathrooms and toilets that are not naturally ventilated.
Sizing a fan for a target
To pick a fan by air changes, switch the calculator to "Airflow for target ACH". A family bathroom of 11.52 m³ at 10 air changes per hour needs 115.2 m³/h, which is 32 L/s, comfortably above the 25 L/s minimum. Add a margin for the duct length and outlet before choosing from the catalogue.
For larger or unusual rooms, commercial kitchens or anything served by central ductwork, the design falls under AS 1668.2 and needs a mechanical engineer or ventilation contractor.
Tools for this job
- Air Changes per Hour Calculator: turns a fan's m³/h into L/s and air changes, and finds the flow for a target ACH.
- Floor Area Calculator: room areas for the 5% natural ventilation test and for odd-shaped rooms.
- Heat Loss Calculator: the heat a room loses through walls and windows, explained in the guide to U-values and heat loss.
- Duct Size Calculator: check the duct can carry the fan's flow, with background in the guide to duct sizing.
Frequently asked questions
Is a 90 m³/h exhaust fan enough for a bathroom?
It meets the NCC minimum of 25 L/s on its rating, but only just. Once ducted it will deliver less, so in anything bigger than a small ensuite a fan rated well above 90 m³/h is the safer choice.
Can a bathroom exhaust fan vent into the roof space?
Not under NCC 2025 Housing Provisions 10.8.2. Exhaust from kitchens, range hoods, bathrooms, toilets and laundries must discharge directly, or through a shaft or duct, to outdoor air.
Does every bathroom fan need a run-on timer?
Only where the bathroom or toilet is not naturally ventilated under 10.6.2 and the fan runs intermittently. Then it must be interlocked with the light and keep running for 10 minutes after the light goes off.
How many air changes per hour should a bathroom get?
The NCC does not set one; it sets 25 L/s. In practice that is about 14 air changes an hour in a small ensuite and about 8 in a 2.4 by 2.0 m bathroom. Higher air change rates clear steam faster.
Sources and further reading
- Part 10.8 Condensation management, Australian Building Codes Board (NCC 2025 Housing Provisions). 10.8.2 exhaust rates, discharge, run-on timers and make-up air.
- Part 10.6 Ventilation, Australian Building Codes Board (NCC 2025 Housing Provisions). The 5% natural ventilation rule and mechanical alternatives.
- Part 13.4 Building sealing, Australian Building Codes Board (NCC 2025 Housing Provisions). Sealing devices on exhaust fans.
- NCC 2025 Condensation in buildings handbook, Australian Building Codes Board. Background on managing condensation in homes.
- Appendix B: Air, US CDC. Time to remove airborne contaminants at each air change rate.
- Standards 62.1 and 62.2, ASHRAE. The US ventilation standards behind the original guide.