Air Changes per Hour and HRV Sizing for Canadian Homes
How the National Building Code sizes an HRV or principal fan by bedrooms, what bathroom and kitchen fans need in L/s and cfm, and what that means in air changes.
By Redbison Dev · · 9 min read

Canada edition. Written for Canadian houses under Part 9 of the National Building Code of Canada 2025, with principal fan rates by bedrooms, supplemental fans in L/s and cfm, the one air change summer rule, ACH50 for energy modelling and Health Canada guidance. US edition
A Canadian house is not ventilated to a target number of air changes per hour. Under Part 9 of the National Building Code of Canada (NBC), heating-season ventilation comes from a principal ventilation fan, often the exhaust side of an HRV or ERV, sized by the number of bedrooms: 22 to 32 L/s for a three-bedroom home, for example. That works out to only about 0.2 to 0.3 air changes an hour. This guide converts the code's litres per second and the cfm on fan boxes into air changes, using the Canadian version of the Air Changes per Hour Calculator.
Why the code moved away from air changes
The NBC used to ask for a whole-house rate as a fraction of volume: 0.5 air changes per hour in the 1985 edition and 0.3 in the 1990 edition, according to the code's own explanatory note on ventilation history. The current code sizes the principal fan by bedrooms instead, because, in the words of Note A-9.32.3.3.(2), "the amount of ventilation required is related to the activities of people", and the number of people usually follows the number of bedrooms rather than the size of the house.
The same note explains the maximum. A fan much bigger than the household needs tends to be switched off for noise or heating cost, so the code caps it.
The principal ventilation fan
NBC 2025 Table 9.32.3.3 gives the "normal operating exhaust capacity" of the principal fan:
| Bedrooms | Minimum | Maximum | Minimum in cfm |
|---|---|---|---|
| 1 | 16 L/s | 24 L/s | 33.9 cfm |
| 2 | 18 L/s | 28 L/s | 38.1 cfm |
| 3 | 22 L/s | 32 L/s | 46.6 cfm |
| 4 | 26 L/s | 38 L/s | 55.1 cfm |
| 5 | 30 L/s | 45 L/s | 63.6 cfm |
| More than 5 | Design to CSA F326 or Part 6 |
The fan must be approved for continuous operation and have a manual switch in the living area marked "VENTILATION FAN" (Sentence 9.32.3.3.(5)). A dehumidistat can run it automatically, but the manual switch must be able to turn it on regardless.
What that means in air changes
Take a three-bedroom, 155 m² house (about 1,670 ft²) with 2.4 m ceilings, 372 m³ in all. The calculator gives:
| Principal fan | m³/h | Air changes per hour |
|---|---|---|
| 22 L/s (table minimum) | 79.2 | 0.21 |
| 32 L/s (table maximum) | 115.2 | 0.31 |
Health Canada's guide to ventilation and the indoor environment describes a similar outcome from a different angle: about 5 to 10 L/s per occupant, or "roughly a complete house air change every three hours". It also recommends running the system continuously at low to medium capacity for most of the year in newer houses.
Bathroom and kitchen fans
Supplemental fans come on top of the principal fan (Article 9.32.3.7):
- Kitchen: at least 50 L/s (106 cfm), unless the principal fan's only intake is in the kitchen, or it draws from the kitchen and other rooms and can be switched to 2.5 times its minimum capacity from a switch marked "KITCHEN EXHAUST".
- Bathroom or water-closet room: at least 25 L/s (53 cfm) wherever the principal fan has no exhaust intake in that room.
- Each supplemental fan needs a manual switch in the room it serves.
For the three-bedroom house, the kitchen exemption means a principal fan with a high speed of at least 2.5 x 22 = 55 L/s.
| Room | Size | Fan | Air changes per hour | Time to clear 99% |
|---|---|---|---|---|
| Bathroom | 2.4 x 1.5 x 2.4 m (8.6 m³) | 25 L/s (90 m³/h) | 10.4 | about 27 minutes |
| Kitchen | 4.0 x 3.5 x 2.4 m (33.6 m³) | 50 L/s (180 m³/h) | 5.36 | about 52 minutes |
The clearing times assume clean incoming air that mixes fully with the room. Under that assumption the concentration of steam or cooking fumes falls as e^(−ACH x hours), so each air change removes 63% of what remains and 99% takes 4.6 air changes. That is why the run time matters more than the rating: Health Canada reports that bathroom fans are typically operated for under 30 minutes a day and range hoods for about 15 to 45 minutes, and it suggests a timer, or running a quiet ensuite fan overnight.
The rating is a lab figure. A long duct, tight elbows or a crushed flex run through the attic cuts the real flow, so a fan sold as 50 cfm in a bathroom that needs 53 cfm is already short before it is ducted.
Summer: the one air change per hour rule
Air changes per hour appear directly in the code for the non-heating season. A habitable room with no openable window to the outdoors (natural ventilation under Table 9.32.2.2) needs mechanical ventilation:
- if it is not air conditioned, a fan able to exhaust or supply one air change per hour (Sentence 9.32.2.3.(3));
- if it is mechanically cooled, the rates in Table 9.32.2.3 (for example 10 L/s for the main bedroom and 5 L/s for a recreation room) or a system to Subsection 9.32.3.
A basement recreation room 8 m by 6 m with a 2.3 m ceiling holds 110.4 m³. With no window and no air conditioning, one air change per hour is 110.4 m³/h: 30.7 L/s, or 65 cfm. Enter the room in the calculator, choose "Airflow for target ACH" and type 1. If the same basement is air conditioned, the Table 9.32.2.3 rate of 5 L/s applies instead.
ACH50 is about leaks, not ventilation
Blower-door results in Canada are usually quoted as ACH50, air changes per hour at a 50 Pa pressure difference. They appear in the energy efficiency part of the code, not the ventilation part. When a house is modelled under the performance path of Section 9.36 and is not tested, the code assumes 3.2 ACH50, or 2.5 ACH50 where the air barrier meets the listed details; a tested house can use its measured value (Sentence 9.36.6.10.(9)).
A low ACH50 is a reason to make sure the principal fan runs, not a sign that the house is ventilated. Under normal weather the pressure across the walls is a few pascals, so natural leakage is a small fraction of the test figure.
Fuel-burning appliances and depressurization
Big exhaust fans pull the house negative. Article 9.32.3.8 applies extra protection, such as make-up air, in a dwelling with a fuel-fired furnace or water heater that is not direct-vented or mechanically vented. Check it before adding a high-capacity range hood to an older house with a natural-draft water heater, and have a licensed gas fitter look at it.
Your province's code
The NBC is a model code. Provinces and territories adopt it, often with changes and sometimes in an earlier edition, and some publish their own building code. The figures here come from NBC 2025; confirm the edition enforced where you build with your municipal building department.
Tools for this job
- Air Changes per Hour Calculator: turns fan L/s or cfm into air changes, finds the flow for the one air change rule, and shows the Table 9.32.3.3 principal fan range.
- Floor Area Calculator: floor area and volume in square feet or square metres for odd-shaped rooms.
- Heat Loss Calculator: the fabric heat loss that ventilation adds to; the guide to U-values, R-values and heat loss explains how they combine.
- Duct Size Calculator: check the duct can carry the fan's flow, with background in the guide to duct sizing.
Frequently asked questions
How big should the HRV be for a four-bedroom house?
Under NBC 2025 Table 9.32.3.3, the principal fan, which can be the exhaust side of an HRV, needs a normal operating exhaust capacity of 26 to 38 L/s (55 to 81 cfm) for four bedrooms. Houses with more than five bedrooms are designed to CSA F326 or Part 6.
Is a 50 cfm bathroom fan enough?
Not on paper. The NBC asks for at least 25 L/s, which is 53 cfm, in a bathroom where the principal fan has no intake. Pick a fan rated above 53 cfm at a realistic static pressure, since the duct will cut the delivered flow.
Can the HRV replace the kitchen fan?
Yes, if it can be switched to 2.5 times its minimum capacity from a switch in the kitchen marked "KITCHEN EXHAUST", or if its only intake is in the kitchen. Otherwise a 50 L/s kitchen fan is needed.
How many cfm is 30 L/s?
About 64 cfm. One L/s is 2.119 cfm, and one cfm is 0.472 L/s. Multiply L/s by 3.6 for m³/h.
Sources and further reading
- National Building Code of Canada 2025, National Research Council Canada. Subsections 9.32.2 and 9.32.3, Article 9.36.6.10 and Notes A-9.32.3.3 and A-9.36.7.3.(7).
- National Building Code of Canada 2025 (catalogue record), Government of Canada Publications.
- Ventilation and the indoor environment, Health Canada. Continuous HRV use, fan run times, humidity below 50% and 5 to 10 L/s per occupant.
- Residential indoor air quality guidelines, Health Canada. Carbon dioxide at 1,000 ppm (24-hour average) and other indoor limits.
- Appendix B: Air, US CDC. Time to remove airborne contaminants at each air change rate.
- Standards 62.1 and 62.2, ASHRAE. Among the good practice the NBC cites for ventilation design.
Open the Air Changes per Hour Calculator