Air Changes per Hour and Part F Extract Rates in UK Homes
Turn extract fan l/s into air changes per hour, check Part F rates for bathrooms and kitchens, the four ACH purge rule and the whole dwelling rate for a UK home.
By Redbison Dev · · 9 min read

United Kingdom edition. Written for homes in England, with Approved Document F extract and whole dwelling rates in l/s, the four air change purge and windowless wet room rules, HSE carbon dioxide guidance and metric rooms. US edition
In England, ventilation for a house or flat is set out in Approved Document F, and it speaks mostly in litres per second, not air changes per hour. An intermittent bathroom fan needs 15 l/s, a kitchen 30 l/s with a cooker hood ducted outside or 60 l/s without one, and every habitable room needs purge ventilation of at least four air changes an hour. This guide shows how the two ways of counting meet, using the UK version of the Air Changes per Hour Calculator with rooms in metres.
Litres per second, cubic metres per hour and ACH
Fan boxes in UK shops quote flow in m³/h or l/s, sometimes both. Approved Document F uses l/s. The conversions are simple:
m³/h = l/s x 3.6
ACH = airflow (m³/h) / room volume (m³)
A bathroom 2.2 m by 1.8 m with a 2.4 m ceiling holds 9.5 m³. A fan delivering exactly the Part F minimum of 15 l/s moves 54 m³/h, so:
ACH = 54 / 9.504 = 5.68
That is one room's worth of air every 10.6 minutes. Type the room into the calculator in metres and enter 54 as the flow in m³/h to see the same figure.
Two cautions before you trust that number. The rating on the box is usually a free-air figure; a long run of flexible duct to a soffit can take a large share of it away. And Approved Document F asks for flow rates to be measured once a mechanical system is installed, with the results given to building control, so the installed figure is the one that counts.
What Approved Document F asks for
The 2021 edition of Approved Document F, Volume 1 (dwellings) sets these minimum extract rates for intermittent fans in Table 1.1, and the high rates for continuous extract systems in Table 1.2:
| Room | Intermittent fan (Table 1.1) | Continuous system, high rate (Table 1.2) |
|---|---|---|
| Kitchen, cooker hood ducted outside | 30 l/s | 13 l/s |
| Kitchen, no hood or hood not ducted outside | 60 l/s | 13 l/s |
| Utility room | 30 l/s | 8 l/s |
| Bathroom | 15 l/s | 8 l/s |
| WC (sanitary accommodation) | 6 l/s | 6 l/s |
A recirculating cooker hood on its own does not count as ventilation under Part F, which is why the kitchen without a ducted hood needs double the rate. A 2026 edition has been published that takes effect on 24 March 2027 for most building work in England; it keeps these rates and the four air change purge rule, with some paragraphs renumbered.
Purge: the place ACH appears
Paragraph 1.27 asks for purge ventilation in each habitable room "capable of extracting at least four air changes per hour". Purge is for clearing paint fumes, burnt toast or smoke quickly, and it is normally met with an opening window of the size given in Table 1.4, not a fan. For a lounge 4.5 m by 3.6 m with a 2.4 m ceiling (38.9 m³), four air changes is 155.5 m³/h, or 43.2 l/s.
Bathrooms with no outside wall
Internal bathrooms and en-suites catch people out. Paragraph 1.48 says that if a wet room has no external walls, its intermittent fan should extract at four air changes per hour, and paragraph 1.51 asks for the fan to keep running for at least 15 minutes after the room is vacated when there is no openable window. So the fan must meet both 15 l/s and four ACH, whichever is higher:
| Internal bathroom | Volume | Four ACH needs | Governs |
|---|---|---|---|
| 2.2 x 1.8 x 2.4 m | 9.5 m³ | 38.0 m³/h (10.56 l/s) | 15 l/s from Table 1.1 |
| 3.0 x 2.5 x 2.4 m | 18.0 m³ | 72.0 m³/h (20.0 l/s) | 20 l/s from the four ACH rule |
A 15 l/s fan in the larger room gives only 3 ACH, so a builder who fits the cheapest compliant-looking fan to a big internal shower room can fall short. Use the calculator's "Airflow for target ACH" mode with a target of 4 to find the figure.
The whole dwelling rate
Background ventilation for the home as a whole, through trickle vents or a continuous system, is set by paragraph 1.24 and Table 1.3. The rate is the higher of:
- 0.3 l/s per m² of internal floor area, all storeys added together; and
- a figure by bedrooms: 19, 25, 31, 37 and 43 l/s for one to five bedrooms, plus 6 l/s for each further bedroom (13 l/s for a home with a single habitable room).
| Home | By floor area | By bedrooms | Whole dwelling rate |
|---|---|---|---|
| Three-bedroom semi, 85 m² | 25.5 l/s | 31 l/s | 31 l/s (bedrooms govern) |
| Two-bedroom flat over two levels, 150 m² | 45 l/s | 25 l/s | 45 l/s (area governs) |
With 2.4 m ceilings the semi holds 204 m³, so 31 l/s (111.6 m³/h) is about 0.55 air changes per hour. Appendix B of the same document assumes only 0.15 ACH of infiltration through cracks and gaps in a less airtight home, and none in a highly airtight one. That gap is why a well-sealed new build cannot rely on leaks for fresh air.
Airtightness changes the system you need
Part F links the type of system to how leaky the home is. A dwelling with a design air permeability above 5 m³/(h·m²) at 50 Pa, or an as-built figure above 3, counts as less airtight and can use background ventilators with intermittent fans. Tighter homes are steered to continuous mechanical extract or mechanical ventilation with heat recovery (MVHR), and a naturally ventilated home that tests tighter than designed needs expert advice or continuous extract.
Note the unit. UK air tests report air permeability per square metre of envelope area, not the ACH50 figure common in North America and in Passivhaus, so the two numbers cannot be compared directly without the home's envelope area and volume.
How fast air changes actually clear a room
If incoming air is clean and mixes fully with the room, a pollutant falls exponentially:
C / C0 = e^(−ACH x t)
with t in hours. One air change leaves 37% behind, and clearing 99% takes ln(100) = 4.6 air changes. Approved Document F's performance criteria make the same full-mixing assumption (ventilation effectiveness of 1.0).
| Room | ACH | Time to clear 99% |
|---|---|---|
| Bathroom at 15 l/s (9.5 m³) | 5.68 | about 49 minutes |
| Lounge at four ACH purge | 4 | about 69 minutes |
| Kitchen-diner 6 x 4 x 2.4 m with a 30 l/s hood | 1.88 | about 2 hours 27 minutes |
| Same room, 60 l/s wall fan | 3.75 | about 74 minutes |
The kitchen-diner shows why the 15-minute run-on and leaving the fan on after a shower matter more than the label rate. Steam in an open-plan room is only captured well close to the hood, at its high setting, while cooking.
Offices, classrooms and carbon dioxide
Workplaces are different. Regulation 6 of the Workplace (Health, Safety and Welfare) Regulations requires every enclosed workplace to be ventilated by "a sufficient quantity of fresh or purified air", and the Health and Safety Executive's guidance on carbon dioxide monitors says readings consistently above 1,500 ppm in an occupied room indicate poor ventilation. HSE also notes that about 1,000 ppm corresponds to roughly 10 litres per second per person. Commercial design works in l/s per person and per m², not ACH, so treat a room ACH figure as a check rather than the design basis there.
Tools for this job
- Air Changes per Hour Calculator: ACH from a fan's m³/h, the flow for a purge or windowless-room target, and the Approved Document F whole dwelling rate.
- Floor Area Calculator: the internal floor area of all storeys for the 0.3 l/s per m² test.
- Heat Loss Calculator: the fabric heat loss that ventilation adds to, explained in the guide to U-values and heat loss.
- Duct Size Calculator: check that the duct run can carry the fan's flow, with the background in the guide to duct sizing.
Frequently asked questions
Is 15 l/s enough for a bathroom with no window?
Only if the room is small. A windowless wet room with no external wall also needs four air changes per hour and a 15-minute run-on. In a 3.0 by 2.5 m room with a 2.4 m ceiling, four ACH is 20 l/s, so a 15 l/s fan falls short.
Does a recirculating cooker hood meet Part F?
No. Approved Document F says a recirculating hood on its own does not provide ventilation that complies. Without a hood ducted outside, the kitchen needs a 60 l/s intermittent fan, or a continuous system with a 13 l/s high rate.
How many l/s is a 100 m³/h fan?
27.8 l/s. Divide m³/h by 3.6 for litres per second. In a 9.5 m³ bathroom a 100 m³/h fan gives about 10.5 air changes per hour, before any loss through the duct.
Do these rates apply in Scotland, Wales and Northern Ireland?
No. Approved Document F applies in England. Wales has its own Approved Document F, Scotland uses Section 3 of the Building Standards Technical Handbooks and Northern Ireland uses Technical Booklet K, so check the guidance where the home is. A building control body or a ventilation installer can confirm what applies to a particular job.
Sources and further reading
- Ventilation: Approved Document F, GOV.UK. Volume 1 for dwellings in the 2021 and 2026 editions.
- Approved Document F Volume 1, 2021 edition (PDF), GOV.UK. Tables 1.1 to 1.3, paragraphs 1.24, 1.27, 1.48 and 1.51, and Appendix B assumptions.
- Approved Document F Volume 1, 2026 edition (PDF), GOV.UK. Takes effect on 24 March 2027 for most building work.
- Using CO2 monitors, Health and Safety Executive. The 1,500 ppm sign of poor ventilation and 1,000 ppm as about 10 l/s per person.
- Ventilation in the workplace, Health and Safety Executive. The legal duty to ventilate enclosed workplaces.
- Overheating: Approved Document O, GOV.UK. Why new homes may need more purge than Part F's four air changes.
- Appendix B: Air, US CDC. Time to remove airborne contaminants at a given air change rate.
Open the Air Changes per Hour Calculator
More HVAC & Plumbing
Every tool in the HVAC & Plumbing section, free and in your browser.